Goodman Mfg IO-367B installation instructions Rigging Details

Models: IO-367B

1 20
Download 20 pages 14.7 Kb
Page 7
Image 7
RIGGING DETAILS

RIGGING DETAILS

Manual backgroundWARNING

TO PREVENT PROPERTY DAMAGE, THE UNIT SHOULD REMAIN IN AN UPRIGHT POSITION DURING ALL RIGGING AND MOVING OPERATIONS. TO FACILITATE LIFTING AND MOVING WHEN A CRANE IS USED, PLACE THE UNIT IN AN ADEQUATE CABLE SLING.

Manual backgroundCAUTION

DO NOT LIFT UNITS TWO AT A TIME. PROVISIONS FOR FORKS HAVE BEEN INCLUDED IN THE UNIT BASE FRAME. MINIMUM FORK LENGTH IS 72” TO PREVENT DAMAGE TO THE UNIT.

Provisions for forks have been included in the unit base frame. No other fork locations are approved.

Manual backgroundWARNING

TO PREVENT POSSIBLE EQUIPMENT DAMAGE, PROPERTY DAMAGE, PERSONAL INJURY OR DEATH, THE FOLLOWING BULLET POINTS MUST BE OBSERVED WHEN INSTALLING THE UNIT.

• Unit must be lifted by the four lifting holes located at

the base frame corners.

• Lifting cables should be attached to the unit with

shackles.

• The distance between the crane hook and the top of

the unit must not be less than 60”.

• Two spreader bars must span over the unit to prevent

Manual background CAUTION

WHEN UNIT IS SUSPENDED, BOARDS AND SHIPPING BRACE WILL DROP WHEN SCREWS ARE REMOVED. TO PREVENT PERSONAL INJURY, STAND CLEAR. REMOVE FORK HOLE BRACKETS, BOARDS AND SHIPPING BRACE FROM BOTTOM OF UNIT BEFORE PLACING UNIT ONTO CURB.

To assist in determining rigging requirements, unit weights are shown as follows:

damage to the cabinet by the lift cables. Spreader

bars must be of sufficient length so that cables do not

come in contact with the unit during transport.

Remove wood struts mounted beneath unit base

frame before setting unit on roof curb. These struts

are intended to protect unit base frame from fork lift

damage. Removal is accomplished by extracting the

sheet metal retainers and pulling the struts through

the base of the unit. Refer to rigging label on the unit.

Important: If using bottom discharge with roof curb, duct- work should be attached to the curb prior to installing the unit. Ductwork dimensions are shown in Roof Curb Installa- tion Instructions.

Refer to the Roof Curb Installation Instructions for proper curb installation. Curbing must be installed in compliance with the National Roofing Contractors Association Manual.

A

 

Y

COMPRESSOR 1

 

 

CG

 

COMPRESSOR 2

B

X

C

SLIO CR OTA

ORP AV

E

D

Lower unit carefully onto roof mounting curb. While rigging unit, center of gravity will cause condenser end to be lower than supply air end.

CORNER & CENTER OF GRAVITY LOCATIONS

7

Page 7
Image 7
Goodman Mfg IO-367B installation instructions Rigging Details