Goodman Mfg IO-367B Appendix B Electrical Data, Attention Installing Personnel

Models: IO-367B

1 20
Download 20 pages 14.7 Kb
Page 18
Image 18
APPENDIX B ELECTRICAL DATA

APPENDIX B ELECTRICAL DATA

ELECTRICAL DATA

 

 

VOLTAGE

 

LARGER

SMALLER

OD FAN MOTORS

 

ID FAN MOTOR

 

VOLTAGE

LIMITATIONS

COMPRESSOR

COMPRESSOR

 

(ea)

 

ID MOTOR

MODELS

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(NAMEPLATE)

MIN

MAX

Qty

 

RLA

LRA

Qty

RLA

LRA

Qty

HP

RLA

APPL

HP

FLA

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

208/230-60-3

187

253

1

 

29.5

195.0

1

25.0

164.0

3

1/3

2.40

BD STD STATIC

3.0

9.2

15 TON

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

460-60-3

414

506

1

 

14.7

95.0

1

12.2

100.0

3

1/3

1.20

BD STD STATIC

3.0

4.6

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

575-60-3

518

633

1

 

12.2

80.0

1

9.0

78.0

3

1/3

0.90

BD STD STATIC

3.0

4.2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ELECTRICAL DATA

 

VOLTAGE

VOLTAGE

COMPRESSOR

OD FAN MOTORS

 

ID FAN

MODELS

LIMITATIONS

 

(ea)

 

 

(ea)

 

ID MOTOR APPL

MOTOR

(NAMEPLATE)

 

 

 

 

 

 

 

 

 

 

MIN

MAX

Qty

RLA

LRA

Qty

HP

RLA

HP

FLA

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

208/230-60-3

187

253

2

33.3

239.0

3

1/3

2.40

BD STD STATIC

5.0

12.7

20 TON

 

 

 

 

 

 

 

 

 

 

 

 

460-60-3

414

506

2

17.9

125.0

3

1/3

1.20

BD STD STATIC

5.0

6.4

 

 

 

 

 

 

 

 

 

 

 

 

 

 

575-60-3

518

633

2

12.8

80.0

3

1/3

0.90

BD STD STATIC

5.0

5.1

 

 

 

 

 

 

 

 

 

 

 

 

 

NOTE: See unit nameplate for proper overcurrent protection.

UNIT

HEATER KIT

MINIMUM CFM

HEATER KIT

MINIMUM CFM

HEATER KIT

MINIMUM CFM

MODEL NUMBER

Downshot

MODEL NUMBER

Downshot

MODEL NUMBER

Downshot

 

 

EHK3-31

5250

EHK4-31

5250

EHK7-31

5250

15 TON

EHK3-46

5250

EHK4-46

5250

EHK7-46

5250

 

EHK3-60

5250

EHK4-60

5250

EHK7-60

5250

 

 

 

 

 

 

 

 

EHK3-31

7000

EHK4-31

7000

EHK7-31

7000

20 TON

EHK3-46

7000

EHK4-46

7000

EHK7-46

7000

 

EHK3-60

7000

EHK4-60

7000

EHK7-60

7000

 

EHK3-75

7000

EHK4-75

7000

EHK7-75

7000

 

 

 

 

 

 

 

When using electric heat kit, use of the single point kit installed in the unit is required to meet UL requirements

ELECTRICAL DATA ATTENTION INSTALLING PERSONNEL

Use only the heater kit specified for each model as dictated by the table above.