APPENDIX A BLOWER PERFORMANCE DATA
BELT DRIVE - STANDARD
CPC180 STANDARD BELT DRIVE
|
|
|
|
|
|
|
|
|
| TURNS OPEN |
|
|
|
|
|
|
|
|
| ||
ESP, In H2O |
| 0 |
| 1 | 2 |
|
| 3 |
| 4 |
| 5 |
| 6 | |||||||
|
|
|
|
|
|
|
| ||||||||||||||
| CFM |
| BHP | CFM |
| BHP | CFM |
| BHP | CFM |
| BHP | CFM |
| BHP | CFM |
| BHP | CFM |
| BHP |
0.2 |
|
|
|
|
| 7203 |
| 2.18 | 6718 |
| 1.94 | ||||||||||
0.4 |
|
|
| 7306 |
| 2.54 | 6777 |
| 2.14 | 6257 |
| 1.80 | 5711 |
| 1.66 | ||||||
0.6 |
| 7477 |
| 2.97 | 6899 |
| 2.51 | 6323 |
| 2.10 | 5716 |
| 1.72 | 5103 |
| 1.39 |
|
| |||
0.8 | 7112 |
| 2.96 | 6467 |
| 2.46 | 5795 |
| 2.01 | 5101 |
| 1.61 |
|
|
| ||||||
1.0 | 5983 |
| 2.38 | 5190 |
| 1.89 |
|
|
|
|
| ||||||||||
1.2 | 4426 |
| 1.71 |
|
|
|
|
|
|
CPC240 STANDARD BELT DRIVE
|
|
|
|
|
|
|
|
|
| TURNS OPEN |
|
|
|
|
|
|
|
|
| ||
ESP, In H2O |
| 0 |
| 1 |
| 2 |
| 3 |
| 4 |
| 5 |
| 6 | |||||||
|
|
|
|
|
|
|
| ||||||||||||||
| CFM |
| BHP | CFM |
| BHP | CFM |
| BHP | CFM |
| BHP | CFM |
| BHP | CFM |
| BHP | CFM |
| BHP |
0.2 |
|
|
|
|
|
| 9664 |
| 4.05 | ||||||||||||
0.4 |
|
|
|
| 9570 |
| 4.08 | 9197 |
| 3.82 | 8702 |
| 3.51 | ||||||||
0.6 |
|
|
| 9038 |
| 3.82 | 8460 |
| 3.46 | 7949 |
| 3.14 |
| ||||||||
0.8 |
| 8171 |
| 2.93 | 7630 |
| 3.70 | 7068 |
| 2.79 |
|
|
| ||||||||
1.0 |
| 7901 |
| 2.85 | 7203 |
| 3.42 |
|
|
|
| ||||||||||
1.2 | 7344 |
| 4.35 |
|
|
|
|
|
|
NOTES:
High static airflow requires installation of high static kit (HSKT240), or
Unit factory shipped with sheave set at 2.5 turns open.
Air flow table represent dry coil with filters installed; SCFM correction factor for wet coil is 4%.
16