BLOWER PERFORMANCE DATA

BLOWER PERFORMANCE DATA

GPC14[24-60]H41A*

Dry Coil Data

Model

Speed

 

Volts

 

 

 

E.S.P (In. of H2O)

 

 

 

 

0.1

0.2

0.3

0.4

0.5

 

0.6

0.7

0.8

 

 

 

 

 

 

 

T1

230

 

CFM

934

759

755

638

581

 

489

-

-

GPC1424H41**

 

 

 

 

 

 

 

 

 

 

 

 

WATTS

95

77

76

73

83

 

90

-

-

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

T2,T3

230

 

CFM

990

837

801

744

696

 

652

601

-

 

 

 

 

 

 

 

 

 

 

 

 

WATTS

107

94

105

110

119

 

133

142

-

 

 

 

 

 

 

 

 

 

 

 

 

 

T4, T5

230

 

CFM

1061

989

947

925

876

 

-

-

-

 

 

 

 

 

 

 

 

 

 

 

 

 

 

WATTS

126

134

146

158

169

 

-

-

-

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

T1

230

 

CFM

1022

929

894

829

797

 

748

695

643

GPC1430H41**

 

 

 

 

 

 

 

 

 

 

 

 

WATTS

116

114

126

134

144

 

156

168

173

 

 

 

 

 

 

 

 

 

 

 

 

 

T2,T3

230

 

CFM

1103

1063

1012

962

937

 

-

-

-

 

 

 

 

 

 

 

 

 

 

 

 

WATTS

142

154

165

173

185

 

-

-

-

 

 

 

 

 

 

 

 

 

 

 

 

 

T4, T5

230

 

CFM

1285

1240

1202

1163

1124

 

1076

1046

1003

 

 

 

 

 

 

 

 

 

 

 

 

 

 

WATTS

205

218

231

244

257

 

268

280

288

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

T1

230

 

CFM

1234

1111

1071

1024

933

 

922

-

-

GPC1436H41**

 

 

 

 

 

 

 

 

 

 

 

 

WATTS

144

140

152

164

179

 

183

-

-

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

T2,T3

230

 

CFM

1287

1232

1186

1133

1099

 

1053

-

-

 

 

 

 

 

 

 

 

 

 

 

 

WATTS

162

175

187

201

213

 

221

-

-

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

T4, T5

230

 

CFM

1381

1325

1277

1233

1181

 

1144

-

-

 

 

 

 

 

 

 

 

 

 

 

 

 

 

WATTS

195

203

217

233

247

 

258

-

-

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

T1

230

 

CFM

1272

1197

1145

1106

1055

 

998

947

906

GPC1442H41**

 

 

 

 

 

 

 

 

 

 

 

 

WATTS

160

168

183

191

211

 

220

230

243

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

T2,T3

230

 

CFM

1357

1297

1244

1194

1147

 

1099

1049

1008

 

 

 

 

 

 

 

 

 

 

 

 

WATTS

188

202

213

228

245

 

255

267

284

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

T4, T5

230

 

CFM

1537

1478

1431

1386

1336

 

1293

1253

1208

 

 

 

 

 

 

 

 

 

 

 

 

 

 

WATTS

244

258

274

288

303

 

317

329

341

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

T1

230

 

CFM

1418

1383

1349

1312

1275

 

1228

1178

1141

GPC1448H41**

 

 

 

 

 

 

 

 

 

 

 

 

WATTS

242

258

273

282

299

 

308

320

338

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

T2,T3

230

 

CFM

1175

1635

1645

1515

1510

 

1450

1430

1400

 

 

 

 

 

 

 

 

 

 

 

 

WATTS

395

420

435

445

455

 

465

470

475

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

T4, T5

230

 

CFM

1845

1790

1715

1685

1590

 

1580

1530

1500

 

 

 

 

 

 

 

 

 

 

 

 

 

 

WATTS

490

505

520

535

550

 

560

570

575

 

 

 

 

 

GPC1460H41**

T1, T2, T3

230

 

CFM

1775

1635

1645

1515

1510

 

1450

1430

1400

 

 

 

 

 

 

 

 

 

 

 

 

WATTS

395

420

435

445

455

 

465

470

475

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

T4, T5

230

 

CFM

2025

1900

1840

1780

1725

 

1650

1620

1580

 

 

 

 

 

 

 

 

 

 

 

 

WATTS

575

595

620

630

645

 

655

660

670

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

NOTES:

1.Data shown is dry coil. Wet coil pressure drop is approx.

2.0.1" H2O, for 2 row indoor coil; 0.2” H2O, for 3 row indoor coil; and 0.3” H2 O, for 4 row indoor coil.

3.Data shown does not include filter pressure drop, approx. 0.08” H2 O.

4.Reduce airflow by 2% for 208V operation.