Goodman Mfg R-410A service manual Package Cooling Specifications, GPC1424-36H41A

Models: R-410A

1 26
Download 26 pages 45.36 Kb
Page 8
Image 8
PACKAGE COOLING SPECIFICATIONS

PACKAGE COOLING SPECIFICATIONS

GPC14[24-36]H41A*

 

 

 

GPC1424H41*

 

GPC1430H41*

GPC1436H41*

 

 

 

 

 

 

 

 

 

 

COOLING

COOLING CAPACITY, BTUH

24,600

 

28,400

35,600

 

 

CAPACITY

SEER / EER

14.5 / 12.1

 

14.0 / 12.0

14.0 / 12.0

 

 

 

 

 

 

 

 

 

 

UNIT

VOLTAGE (NAMEPLATE)

208-230/1/60

 

208-230/1/60

208-230/1/60

 

 

ELECTRICAL

AMPS (TOTAL)

10.5

 

13.16

20.06

 

 

SPECIFICATION

MINIMUM CIRCUIT AMPACITY

12.5

 

15.6

24.2

 

 

 

MAXIMUM OVERCURRENT PROTECTION (1)

20

 

25

40

 

 

COMPRESSOR

TYPE

RECIP

 

RECIP

SCROLL

 

 

 

RATED LOAD AMPS

7.9

 

9.8

16.7

 

 

 

LOCKED ROTOR AMPS

41

 

55

79

 

 

 

 

 

 

 

 

 

 

CONDENSER

HORSEPOWER

1/6

 

1/4

1/4

 

 

FAN MOTOR

RPM

815

 

830

830

 

 

 

FULL LOAD AMPS

1.1

 

1.5

1.5

 

 

 

LOCKED ROTOR AMPS

1.7

 

3.0

3.0

 

 

CONDENSER FAN

BLADE DIAMETER (INCHES) / NUMBER OF BLADES

22 / 3

 

22 / 3

22 / 3

 

 

 

 

 

 

 

 

 

 

CONDENSER

FACE AREA - SQ. FT.

13.4

 

13.4

13.4

 

 

COIL

NUMBER OF ROWS

1

 

1

1

 

 

 

FINS PER INCH

24

 

24

24

 

 

 

 

 

 

 

 

 

 

EVAPORATOR

HORSEPOWER - NO. OF SPEEDS

1/2 - 5

 

1/2 - 5

1/2 - 5

 

 

BLOWER

FULL LOAD AMPS

1.5

 

1.86

1.86

 

 

MOTOR

LOCKED ROTOR AMPS

NA

 

NA

NA

 

 

 

MOTOR SPEED TAP - COOLING

T2

 

T2

T2

 

 

 

RPM

1050

 

1050

1050

 

 

 

 

 

 

 

 

 

 

EVAPORATOR

DIAMETER X WIDTH (INCHES)

10 X 8

 

10 X 8

10 X 8

 

 

BLOWER

HI EFFICIENCY COOLING CFM

850

 

1,050

1,200

 

 

 

5 TON NOMINAL COOLING CFM

NA

 

NA

NA

 

 

 

FAN ONLY COOLING CFM

800

 

950

1,100

 

 

 

MAX EXTERNAL STATIC PRESS ("w.c.)

0.5

 

0.5

0.5

 

 

 

 

 

 

 

 

 

 

EVAPORATOR

FACE AREA - SQ. FT.

5.25

 

4.67

5.2

 

 

COIL

NUMBER OF ROWS

3

 

4

3

 

 

 

FINS PER INCH

16

 

16

14

 

 

 

 

 

 

 

 

 

 

GENERAL

FILTER SIZE - SQ. FT. *

20 x 20 x 1

 

20 x 25 x 1

25 x 25 x 1

 

 

INFORMATION

DRAIN SIZE (INCHES)

3/4"

 

3/4"

3/4"

 

 

 

EXPANSION DEVICE

ORIFICE (0.057)

ORIFICE (0.060)

ORIFICE (0.065)

 

 

 

REFRIGERANT CHARGE R-410A (Oz.)

83

 

78

80

 

 

 

POWER SUPPLY CONDUIT KNOCKOUT SIZE (INCHES)

3/4, 1, 1-1/4

 

3/4, 1, 1-1/4

3/4, 1, 1-1/4

 

 

 

LOW VOLTAGE CONDUIT KNOCKOUT SIZE (INCHES)

1/2

 

1/2

1/2

 

 

 

SHIPPING WEIGHT LBS.

310

 

310

370

 

 

 

OPERATING WEIGHT LBS.

300

 

300

360

 

 

 

 

 

 

 

 

 

(1)Maximum Overcurrent Protection Device: MUST use Time Delay Fuse or HACR type Circuit Breaker of the same size as noted. * Calculated external filter size based on air velocity of 300 ft/min.

Wire size should be determined in accordance with National Electrical Codes. Extensive wire runs will require larger wire sizes.

Unit specifications are subject to change without notice. ALWAYS refer to the units serial plate for the most up-to-date general and electrical information.

IMPORTANT: While this data is presented as a guide, it is important to electrically connect the unit and properly size wires and fuses/circuit breakers in accordance with the National Electrical Code and/or all local codes. Data shown is w/o electric heaters.

All wires and overcurrent protection devices are sized for use with electric heaters only and without WARNING refrigeration. If heaters are not installed with above wire size, overheating and fire could occur. See PACKAGE COOLING SPECIFICATIONS section for minimum circuit ampacity and maximum overcurrent

protection during refrigeration cycle.

8