Product Specifications
Airflow Data
(CFM & Temperature Rise vs. External Static Pressure)
| Motor | Tons |
|
|
|
|
| External Static Pressure, (Inches Water Column) |
|
|
| |||||||||
Model |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||
| 0.1 | 0.2 |
|
| 0.3 |
| 0.4 |
| 0.5 | 0.6 | 0.7 | 0.8 | ||||||||
Speed | AC¹ |
|
|
|
|
| ||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||
|
|
| CFM |
| Rise | CFM |
| Rise | CFM |
| Rise | CFM |
| Rise | CFM |
| Rise | CFM | CFM | CFM |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| T1 | 1½ | 875 |
| 59 | 793 |
| 65 | 736 |
| 70 | 674 |
| 77 | 592 |
| 88 | 556 | 509 | 460 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
GME8 | T2 | 2 | 1,032 |
| 50 | 965 |
| 54 | 914 |
| 57 | 861 |
| 60 | 810 |
| 64 | 756 | 712 | 659 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
T3 | 2½ | 1,217 |
| 43 | 1,153 |
| 45 | 1,098 |
| 47 | 1,051 |
| 49 | 1,009 |
| 51 | 964 | 918 | 877 | |
0703BXC* |
|
|
|
|
| |||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
T4 | 3 | 1,365 |
| 38 | 1,313 |
| 39 | 1,268 |
| 41 | 1,221 |
| 42 | 1,172 |
| 44 | 1,129 | 1,086 | 1,054 | |
|
|
|
|
|
| |||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| T5 | 3½ | 1,549 |
| 33 | 1,505 |
| 34 | 1,460 |
| 36 | 1,420 |
| 37 | 1,378 |
| 38 | 1,350 | 1,305 | 1,268 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| T1 | 2½ | 1,268 |
| 53 | 1,198 |
| 56 | 1,151 |
| 58 | 1,092 |
| 61 | 1,041 |
| 64 | 988 | 932 | 883 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
GME8 | T2 | 3 | 1,362 |
| 49 | 1,305 |
| 51 | 1,261 |
| 53 | 1,212 |
| 55 | 1,170 |
| 57 | 1,121 | 1,074 | 1,021 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
T3 | 3½ | 1,576 |
| 42 | 1,519 |
| 44 | 1,473 |
| 45 | 1,426 |
| 47 | 1,398 |
| 48 | 1,341 | 1,290 | 1,252 | |
0905CXC* |
|
|
|
|
| |||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
T4 | 4 | 1,755 |
| 38 | 1,711 |
| 39 | 1,657 |
| 40 | 1,627 |
| 41 | 1,579 |
| 42 | 1,548 | 1,502 | 1,463 | |
|
|
|
|
|
| |||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| T5 | 5 | 2,183 |
| 31 | 2,128 |
| 31 | 2,094 |
| 32 | 2,060 |
| 32 | 2,014 |
| 33 | 1,992 | 1,944 | 1,847 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| T1 | 3 | 1,466 |
| 58 | 1,415 |
| 60 | 1,357 |
| 63 | 1,306 |
| 65 | 1,248 |
| 68 | 1,202 | 1,144 | 1,088 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
GME8 | T2 | 3½ | 1,642 |
| 52 | 1,596 |
| 53 | 1,552 |
| 55 | 1,499 |
| 57 | 1,449 |
| 59 | 1,388 | 1,352 | 1,306 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
T3 | 4 | 1,750 |
| 49 | 1,750 |
| 49 | 1,707 |
| 50 | 1,667 |
| 51 | 1,610 |
| 53 | 1,574 | 1,531 | 1,486 | |
1155CXC* |
|
|
|
|
| |||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
T4 | 4 | 1,870 |
| 46 | 1,805 |
| 47 | 1,782 |
| 48 | 1,737 |
| 49 | 1,701 |
| 50 | 1,656 | 1,606 | 1,571 | |
|
|
|
|
|
| |||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| T5 | 5 | 2,297 |
| 37 | 2,297 |
| 37 | 2,224 |
| 38 | 2,106 |
| 40 | 2,014 |
| 42 | 1,896 | 1,813 | 1,669 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
¹ @ 0.5” ESP
Notes
•CFM in chart is without filter(s). Filters do not ship with this furnace, but must be provided by the installer. If the furnace requires two return filters, this chart assumes both filters are installed.
•All furnaces ship as
•For most jobs, about 375 - 400 CFM per ton when cooling is desirable.
•INSTALLATION IS TO BE ADJUSTED TO OBTAIN TEMPERATURE RISE WITHIN THE RANGE SPECIFIED ON THE RATING PLATE.
•This chart is for information only. For satisfactory operation, external static pressure should not exceed value shown on the rating plate.
•The above chart is for U.S. furnaces installed at
•Factory Motor Speed Setting: T1 = 1st Stage Ht, T2 = 2nd Stage Ht, T5 = Cooling
•Tempertaure rise data is based on
www.goodmanmfg.com | 5 |