Goodman Mfg SSZ 14 SEER SSZ14018,30,42,48,601AF SSZ140241AJ SSZ140361AH, Heat Pump Specifications

Models: SSZ 14 SEER

1 28
Download 28 pages 50.9 Kb
Page 6
Image 6
SSZ140[18,30,42,48,60]1AF; SSZ140241AJ; SSZ140361AH

HEAT PUMP SPECIFICATIONS

SSZ140[18,30,42,48,60]1AF; SSZ140241AJ; SSZ140361AH

Cooling Capacity, BTUH

Compressor

R.L. Amps

L.R. Amps

Low Pressure Switch

Open

Close

High Pressure Switch

Open

Close

Condenser Fan Motor

Horsepower

F.L. Amps

Liquid Line, Inches O.D.*

Suction Line, Inches O.D.* Refrigerant Charge

Power Supply

Minimum Circuit Ampacity(1) Maximum Overcurrent Device(2)

Electrical Conduit Size

Power Supply (Inches)

Approximate Shipping W eight

SSZ140181AF

SSZ140241AJ

SSZ140301AF

SSZ140361AH

SSZ140421AF

SSZ140481AF

SSZ140601AF

 

 

 

 

 

 

 

18,000

24,000

30,000

36,000

42,000

48,000

60,000

 

 

 

 

 

 

 

9.0

12.82

14.10

16.67

17.95

19.9

26.41

48.0

58.3

73.0

79.0

112.0

109.0

130.0

22 PSIG

22 PSIG

22 PSIG

22 PSIG

22 PSIG

22 PSIG

22 PSIG

50 PSIG

50 PSIG

50 PSIG

50 PSIG

50 PSIG

50 PSIG

50 PSIG

610 PSIG

610 PSIG

610 PSIG

610 PSIG

610 PSIG

610 PSIG

610 PSIG

420 PSIG

420 PSIG

420 PSIG

420 PSIG

420 PSIG

420 PSIG

420 PSIG

 

 

 

 

 

 

 

1/12

1/6

1/6

1/4

1/4

1/4

1/4

0.6

1.1

1.0

1.5

1.5

1.5

1.5

 

 

 

 

 

 

 

3/8"

3/8"

3/8"

3/8"

3/8"

3/8"

3/8"

3/4"

3/4"

3/4"

7/8"

7/8"

7/8"

7/8"

140.0

160.0

185.0

210.0

210.0

270.0

275.0

 

 

 

 

 

 

 

208/230-60-1

208/230-60-1

208/230-60-1

208/230-60-1

208/230-60-1

208/230-60-1

208/230-60-1

11.90

17.10

18.60

22.40

23.90

26.40

34.50

20

25

30

30

40

40

60

 

 

 

 

 

 

 

1/2 or 3/4

1/2 or 3/4

1/2 or 3/4

1/2 or 3/4

1/2 or 3/4

1/2 or 3/4

1/2 or 3/4

199

207

219

242

242

266

280

 

 

 

 

 

 

 

 

 

 

 

 

 

 

*Up to 24' in equivalent line length

(1)Wire size should be determined in accordance with National Electrical Codes; extensive wire runs will require larger wire sizes.

(2)Maximum Overcurrent Protection Device: MUST use Time Delay Fuse or HACR type Circuit Breaker of the same size as noted.

NOTES:

Always check the S & R plate for electrical data on the unit being installed.

Installer will need to supply 7/8" to 1-1/8" adapters for suction line connections (4 & 5 ton units).

Installer will need to supply 3/4" to 7/8" adapters for suction line connections (3 ton unit).

Unit is charged with refrigerant for 15' of 3/8" liquid line. System charge must be adjusted per Installation Instructions Final Charge Procedure.

Installation of these units requires the specified TXV Kit to be installed on the indoor coil. THE SPECIFIED TXV IS DETERMINED BY THE OUTDOOR UNIT, NOT THE INDOOR COIL.

NOTE: This data is provided as a guide, it is important to electrically connect the unit and properly size fuses/ circuit breakers and wires in accordance with all national and/or local electrical codes. Use copper wire only.

6