14

MODEL: GPH1324H41**

 

 

 

 

EXPANDED PERFORMANCE DATA

 

 

 

 

COOLING OPERATION

 

 

Design Subcooling, 12±3 °F @ the liquid access fitting connection AHRI 95 test conditions. Design Superheat 8±3 °F @ the compressor suction access fitting connection.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Outdoor Ambient Temperature

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

65

 

 

 

75

 

 

 

85

 

 

 

95

 

 

 

105

 

 

115

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Entering Indoor Wet

Bulb Temperature

 

 

 

 

 

 

 

 

 

 

 

IDB*

 

Airflow

 

59

63

 

67

71

59

63

 

67

71

59

63

 

67

71

59

63

 

67

71

59

 

63

67

71

59

63

 

67

71

 

 

 

MBh

24.3

24.9

 

26.6

28.4

23.8

24.3

 

26.0

27.7

23.2

23.7

 

25.3

27.1

22.6

23.1

 

24.7

26.4

21.5

 

22.0

23.5

25.1

19.9

20.4

 

21.8

23.3

 

 

 

S/T

1.00

0.94

0.76

0.57

1.00

1.00

0.79

0.59

1.00

1.00

0.81

0.61

1.00

1.00

0.84

0.63

1.00

 

1.00

0.87

0.65

1.00

1.00

 

0.88

0.65

 

 

980

Delta T

23

22

19

15

22

23

19

15

22

22

19

15

21

22

19

16

20

 

21

19

15

19

19

 

18

14

 

 

KW

1.73

1.77

1.82

1.88

1.86

1.90

1.96

2.03

1.98

2.02

2.08

2.15

2.08

2.12

2.19

2.26

2.17

 

2.21

2.28

2.36

2.24

2.29

 

2.36

2.44

 

 

 

AMPS

7.4

7.5

7.7

8.0

7.9

8.0

8.3

8.5

8.5

8.6

8.9

9.2

9.0

9.2

9.4

9.8

9.5

 

9.7

10.0

10.3

10.0

10.2

 

10.5

10.9

 

 

 

HI PR

246

265

280

292

277

298

314

328

315

339

357

373

358

386

407

425

403

 

434

458

478

445

479

 

506

528

 

 

 

LO PR

114

122

133

141

121

129

140

149

126

134

146

155

132

140

153

163

138

 

147

161

171

143

152

 

166

177

 

 

 

MBh

23.6

24.1

25.8

27.6

23.1

23.6

25.2

26.9

22.5

23.0

24.6

26.3

22.0

22.5

 

24.0

25.7

20.9

 

21.3

22.8

24.4

19.3

19.8

 

21.1

22.6

 

 

 

S/T

0.95

0.89

0.73

0.54

0.99

0.93

0.75

0.56

1.00

0.95

0.77

0.58

1.00

0.98

 

0.80

0.60

1.00

 

1.00

0.83

0.62

1.00

1.00

 

0.84

0.62

80

 

875

Delta T

24

23

20

16

24

23

20

16

24

23

20

16

23

23

 

20

16

22

 

22

20

16

20

21

 

19

15

 

KW

1.72

1.76

1.81

1.87

1.85

1.89

1.95

2.01

1.96

2.00

2.07

2.14

2.06

2.11

 

2.18

2.25

2.15

 

2.19

2.27

2.34

2.22

2.27

 

2.34

2.42

 

 

 

AMPS

7.3

7.5

7.7

7.9

7.8

8.0

8.2

8.5

8.4

8.6

8.8

9.1

8.9

9.1

 

9.4

9.7

9.4

 

9.6

9.9

10.2

9.9

10.1

 

10.4

10.8

 

 

 

HI PR

244

263

277

289

274

295

311

325

311

335

354

369

355

382

 

403

420

399

 

429

453

473

441

474

 

501

523

 

 

 

LO PR

113

120

131

140

120

127

139

148

124

132

144

154

131

139

 

152

162

137

 

146

159

169

142

151

 

164

175

 

 

 

MBh

22.5

22.9

24.5

26.2

21.9

22.4

23.9

25.6

21.4

21.9

23.4

25.0

20.9

21.3

 

22.8

24.4

19.8

 

20.3

21.7

23.2

18.4

18.8

 

20.1

21.4

 

 

 

S/T

0.91

0.86

0.70

0.52

0.95

0.89

0.72

0.54

0.97

0.91

0.74

0.55

1.00

0.94

0.76

0.57

1.04

 

0.97

0.79

0.59

1.05

0.98

 

0.80

0.60

 

 

 

Delta T

24

23

20

16

25

24

21

16

25

24

21

17

25

24

21

17

25

 

24

21

16

23

22

 

19

15

 

 

770

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

KW

1.69

1.73

1.78

1.84

1.82

1.86

1.92

1.98

1.93

1.97

2.03

2.10

2.03

2.07

2.14

2.21

2.11

 

2.16

2.23

2.30

2.18

2.23

 

2.31

2.38

 

 

 

AMPS

7.2

7.3

7.5

7.8

7.7

7.8

8.1

8.3

8.3

8.4

8.7

9.0

8.8

8.9

9.2

9.5

9.3

 

9.5

9.7

10.1

9.7

10.0

 

10.3

10.6

 

 

 

HI PR

239

257

272

283

268

289

305

318

305

328

347

362

348

374

395

412

391

 

421

444

464

432

465

 

491

512

 

 

 

LO PR

111

118

129

137

117

125

136

145

122

130

141

151

128

136

149

158

134

 

143

156

166

139

148

 

161

172

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

MBh

24.8

25.2

26.4

28.2

24.2

24.7

25.8

27.6

23.6

24.1

25.2

26.9

23.0

23.5

24.6

26.2

21.9

 

22.3

23.4

24.9

20.3

20.7

 

21.6

23.1

 

 

 

S/T

1.00

1.00

0.91

0.74

1.00

1.00

0.95

0.77

1.00

1.00

0.97

0.79

1.00

1.00

1.00

0.81

1.00

 

1.00

1.00

0.84

1.00

1.00

 

1.00

0.85

 

 

980

Delta T

23

24

23

20

23

23

23

20

22

23

23

20

22

22

23

20

21

 

21

22

20

19

19

 

20

18

 

 

KW

1.75

1.78

1.84

1.90

1.88

1.92

1.98

2.04

1.99

2.04

2.10

2.17

2.10

2.14

2.21

2.28

2.18

 

2.23

2.30

2.38

2.26

2.31

 

2.38

2.46

 

 

 

AMPS

7.4

7.6

7.8

8.0

7.9

8.1

8.3

8.6

8.5

8.7

9.0

9.3

9.0

9.2

9.5

9.8

9.6

 

9.8

10.1

10.4

10.1

10.3

 

10.6

11.0

 

 

 

HI PR

249

268

283

295

279

301

317

331

318

342

361

377

362

389

411

429

407

 

438

463

482

450

484

 

511

533

 

 

 

LO PR

115

123

134

143

122

130

142

151

127

135

147

157

133

142

155

165

140

 

149

162

173

144

154

 

168

179

 

 

 

MBh

24.0

24.5

25.7

27.4

23.5

23.9

25.1

26.8

22.9

23.4

24.5

26.1

22.4

22.8

23.9

25.5

21.2

 

21.7

22.7

24.2

19.7

20.1

 

21.0

22.4

 

 

 

S/T

1.00

0.96

0.87

0.71

1.00

1.00

0.90

0.73

1.00

1.00

0.92

0.75

1.00

1.00

0.95

0.77

1.00

 

1.00

0.99

0.80

1.00

1.00

 

1.00

0.81

85

 

875

Delta T

25

25

23

20

25

25

24

21

24

25

24

21

24

24

24

21

22

 

23

24

20

21

21

 

22

19

 

KW

1.73

1.77

1.82

1.88

1.86

1.90

1.96

2.03

1.98

2.02

2.08

2.15

2.08

2.12

2.19

2.26

2.17

 

2.21

2.28

2.36

2.24

2.29

 

2.36

2.44

 

 

 

AMPS

7.4

7.5

7.7

8.0

7.9

8.0

8.3

8.5

8.5

8.6

8.9

9.2

9.0

9.2

9.4

9.8

9.5

 

9.7

10.0

10.3

10.0

10.2

 

10.5

10.9

 

 

 

HI PR

246

265

280

292

277

298

314

328

315

339

357

373

358

386

407

425

403

 

434

458

478

445

479

 

506

528

 

 

 

LO PR

114

122

133

141

121

129

140

149

126

134

146

155

132

140

153

163

138

 

147

161

171

143

152

 

166

177

 

 

 

MBh

22.8

23.3

24.4

26.0

22.3

22.7

23.8

25.4

21.8

22.2

23.3

24.8

21.2

21.7

22.7

24.2

20.2

 

20.6

21.6

23.0

18.7

19.1

 

20.0

21.3

 

 

 

S/T

0.96

0.92

0.83

0.68

0.99

0.96

0.86

0.70

1.00

0.98

0.89

0.72

1.00

1.00

0.91

0.74

1.00

 

1.00

0.95

0.77

1.00

1.00

 

0.96

0.78

 

 

770

Delta T

26

26

24

21

26

26

25

21

26

26

25

21

25

26

25

21

24

 

25

24

21

22

23

 

23

20

 

 

KW

1.71

1.74

1.80

1.85

1.83

1.87

1.93

1.99

1.95

1.99

2.05

2.12

2.05

2.09

2.16

2.23

2.13

 

2.18

2.25

2.32

2.20

2.25

 

2.32

2.40

 

 

 

AMPS

7.2

7.4

7.6

7.8

7.7

7.9

8.1

8.4

8.3

8.5

8.8

9.0

8.8

9.0

9.3

9.6

9.3

 

9.5

9.8

10.2

9.8

10.0

 

10.3

10.7

 

 

 

HI PR

242

260

275

286

271

292

308

321

308

332

350

365

351

378

399

416

395

 

425

449

468

436

470

 

496

517

 

 

 

LO PR

112

119

130

139

118

126

137

146

123

131

143

152

129

137

150

160

135

 

144

157

168

140

149

 

163

173

 

* Entering Indoor Dry Bulb Temperature

 

 

NOTE: Shaded area is AHRI Rating Conditions

 

 

 

KW = Total system power

 

 

 

 

 

 

 

 

High and low pressures are measured at the liquid and suction access fittings.

 

 

 

 

 

 

 

 

 

AMPS: Unit amps (comp.+ evaporator + condenser fan motors)

 

 

COOLING PERFORMANCE DATA

GPH1324H41**

Page 14
Image 14
Goodmans Package Heat Pump Units, GPH 13 H service manual 105 115 Entering Indoor Wet Bulb Temperature, 24.0

GPH 13 H, Package Heat Pump Units specifications

Goodmans Package Heat Pump Units, specifically the GPH 13 H model, represent an advanced solution in residential and commercial climate control. Known for their efficiency and reliability, these heat pumps offer a combination of heating and cooling capabilities, making them ideal for year-round comfort.

One of the standout features of the GPH 13 H is its energy efficiency rating. With a SEER (Seasonal Energy Efficiency Ratio) of 13, it efficiently converts energy into heating and cooling, which can lead to significant savings on utility bills. This efficiency is not only beneficial for homeowners looking to reduce their energy footprint, but it also qualifies for many energy rebate programs.

Durability is another hallmark of the GPH 13 H. Built with robust materials, the unit is designed to withstand various weather conditions, ensuring longevity and reliable performance. Components are treated to resist corrosion, which extends the lifespan of the heat pump and enhances its efficiency.

The GPH 13 H utilizes innovative inverter technology, allowing it to adjust its cooling and heating output according to the space's specific needs. This results in more consistent temperatures and improved indoor comfort. Additionally, the variable-speed compressor operates at different levels, reducing energy consumption while providing effective heating and cooling.

In terms of installation, the GPH 13 H offers versatility. Its compact design facilitates easy placement in various locations, making it suitable for both new construction and retrofitting existing spaces. The unit's all-in-one design simplifies installation by minimizing the need for external ductwork.

Quiet operation is a critical consideration for many homeowners, and Goodmans excels in this area. The GPH 13 H is engineered to minimize noise levels, ensuring a peaceful indoor environment. This feature makes it an excellent choice for residential areas where noise may be a concern.

The unit also features advanced control systems, including programmable thermostats that allow users to set specific temperature schedules. This feature not only enhances user comfort but also contributes to energy savings by preventing unnecessary heating or cooling when spaces are unoccupied.

Overall, Goodmans Package Heat Pump Units, GPH 13 H, combine efficiency, durability, and advanced technology to deliver a reliable climate control solution. With its focus on energy savings, quiet operation, and flexibility in installation, this model stands out as a leading choice for those seeking optimal home comfort. Its thoughtful design and engineering make it a worthwhile investment in both residential and commercial settings.