PRODUCT DESIGN

ELECTRICAL DATA (*Blower Only, Heat Mode)

All wires and overcurrent protection devices are sized for use with electric heaters only and without
refrigeration. If heaters are not installed with above wire size, overheating and fire could occur. See
PACKAGE COOLING SPECIFICATIONS section for minimum circuit ampacity and maximum overcurrent
protection during refrigeration cycle.
IMPORTANT NOTE: A separate power supply is required for the HKR heater kit.

WARNING

WARNING

GPH1324-1360H41**

Maximum Maximum
Overcurrent Overcurrent
Protection (amps) Protec tion (amps)
at 208 / 240V at 208 / 240V
GPH1324H41**
HKR05*,C* 24 / 27 30 / 30 ---- ---- 4.75 / 16,200
HKR08*,C* 33 / 28 40 / 40 ---- ---- 7.00 / 23,800
HK R10*,C* 45 / 51 60 / 60 ---- ---- 9.50 / 32,400
GPH1330H41**
HKR05*,C* 24 / 27 30 / 30 ---- ---- 4.75 / 16,200
HKR08*,C* 34 / 39 40 / 40 ---- ---- 7.00 / 23,800
HKR10*,C* 45 / 52 60 / 60 ---- ---- 9.50 / 32,400
HK R15*,C* 45 / 52 60 / 60 22 / 25 30 / 30 14.2 5 / 48,600
GPH1336H41**
HKR05*,C* 24 / 27 30 / 30 ---- ---- 4.75 / 16,200
HKR08*,C* 34 / 39 40 / 40 ---- ---- 7.00 / 23,800
HKR10*,C* 45 / 52 60 / 60 ---- ---- 9.50 / 32,400
HK R15*,C* 45 / 52 60 / 60 22 / 25 30 / 30 14.2 5 / 48,600
GPH1342H41**
HKR05*,C* 25 / 27 30 / 30 ---- ---- 4.75 / 16,200
HKR08*,C* 34 / 39 40 / 40 ---- ---- 7.00 / 23,800
HKR10*,C* 46 / 52 60 / 60 ---- ---- 9.50 / 32,400
HKR15*,C* 46 / 52 60 / 60 22 / 25 30 / 3 0 14.25 / 48, 600
HK R20*,C* 46 / 52 60 / 60 43 / 49 60 / 60 19.5 0 / 66,500
GPH1348H41**
HKR05*,C* 25 / 28 30 / 30 ---- ---- 4.75 / 16,200
HKR08*,C* 34 / 40 40 / 40 ---- ---- 7.00 / 23,800
HKR10*,C* 46 / 53 60 / 60 ---- ---- 9.50 / 32,400
HKR15*,C* 46 / 52 60 / 60 22 / 25 30 / 3 0 14.25 / 48, 600
HKR20*,C* 46 / 52 60 / 60 43 / 49 60 / 6 0 19.50 / 66, 500
GPH1360H41**
HKR05*,C* 26 / 30 30 / 30 ---- ---- 4.75 / 16,200
HKR08*,C* 36 / 40 40 / 40 ---- ---- 7.00 / 23,800
HKR10*,C* 48 / 54 60 / 60 ---- ---- 9.50 / 32,400
HKR15*,C* 48 / 54 60 / 60 22 / 25 30 / 3 0 14.25 / 48, 600
HK R20*,C* 48 / 54 60 / 60 43 / 49 60 / 60 19.5 0 / 66,500
Actual
kW & BTU
at 240V
M inimum Circuit
Ampacity
at 208 / 240V
Mi nimum Ci rc uit
Ampacity
at 208 / 240V
Model and Heat Kit Usage
Circuit #1 Circuit #2