Greenheck Fan 240XP-CUb manual Determining CFM cfm, Suggested Air Changes for Proper Ventilation

Models: 240XP-CUb

1 24
Download 24 pages 39.71 Kb
Page 16
Image 16
Determining CFM (cfm)

Determining CFM (cfm)

After the model is known, the cfm must be determined. Consult local code requirements or the table below for suggested air changes for proper ventilation.

The ranges specified will adequately ventilate the corresponding areas in most cases. However, extreme conditions may require “Minutes per Change” outside of the specified range. To determine the actual number needed within a range, consider the geographic location and average duty level of the area. For hot

climates and heavier than normal area usage, select a lower number in the range to change the air more quickly. For moderate climates with lighter usages, select a higher number in the range.

To determine the cfm required to adequately ventilate an area, divide the room volume by the appropriate “Minutes per Change” value.

Suggested Air Changes for Proper Ventilation

 

cfm = Room Volume

Room Volume = L x W x H (of room)

 

 

 

Min./Chg.

 

 

 

Area

Min./Chg.

Area

Min./Chg.

Area

Min./Chg.

Assembly Hall

3-10

Dance Hall

3-7

Machine Shop

3-6

Attic

2-4

Dining Room

4-8

Mill

3-8

Auditorium

3-10

Dry Cleaner

2-5

Office

2-8

Bakery

2-3

Engine Room

1-3

Packing House

2-5

Bar

2-4

Factory

2-7

Projection Room

1-2

Barn

12-18

Foundry

1-5

Recreation Room

2-8

Boiler Room

1-3

Garage

2-10

Residence

2-6

Bowling Alley

3-7

Generator Room 2-5

Restaurant

5-10

Cafeteria

3-5

Gymnasium

3-8

Rest Room

5-7

Church

4-10

Kitchen

1-5

Store

3-7

Classroom

4-6

Laboratory

2-5

Transfer Room

1-5

Club Room

3-7

Laundry

2-4

Warehouse

3-10

Sample problem:

A building requires an exhaust fan to ventilate a general office (see diagram below) which measures 30 ft. x 40 ft. x 8 ft. The office is often crowded.

Solution:

The total room volume is 30 ft. x 40 ft. x 8 ft. = 9600 cubic feet. From the chart, the range for general offices is 2-8 minutes per change. Since the office has heavier than normal usage, 4 minutes per change is recommended. Therefore, the required exhaust is:

9600 ft3 = 2400 cfm

4 min.

Since the air to be exhausted is relatively clean, this is an ideal application for a model GB fan.

Note: In this example, make-up air was provided through a set of louvers at the wall farthest from the exhaust fan. If there were no provisions for make-up air in this room, a supply fan would also have to be sized. The supply cfm should equal the exhaust cfm. Supply fan location should be as far as possible from the exhaust fan.

16

Page 16
Image 16
Greenheck Fan 240XP-CUb manual Determining CFM cfm, Suggested Air Changes for Proper Ventilation