Operation - Recirculating Units (optional)

NOTE

Blower Start-Up, as shown on page 14, should be performed before the blower is run.

Recirculation Operation

The recirculation operation option is recommended when the ventilation equipment provides the primary source of heating for the space. A minimum of 20% outdoor air is mixed with up to 80% filtered recirculated

Building Pressure Control — a

modulating spring return actuator is used to control the return air amounts. The return air damper modulates from fully open to fully closed based on a signal from a remote pressure sensing device.

Turn both knobs to the upper most pressure setting. You may have to remove the outdoor pressure tap tubing. The return air damper should close.

BLOWER

EXHAUST (OPTIONAL)

SUPPLY

 

 

MAIN VALVES

HEAT

 

 

 

DIRTY FILTERS

75

70

 

80

65

(OPTIONAL)

85

60

90

55

 

PHOTOHELIC

GREENHECK

With Maxitrol 44 Room Thermostat

Building

Pressure Control

air. Control strategies include 2-position and modulating dampers.

Before the unit is left in service, the recirculation control system should be tested.

Set both knobs at the lowest setting and the damper should open. It may take one to two minutes for the damper to reach the desired position.

Reset the correct pressure limits before starting the unit.

2-Position Damper

A 2-position spring return actuator is used to control the return air amounts. The

damper moves from open to closed. If power is cut to the unit, the outdoor air damper will fail to close.

Turn the recirculating switch on

 

 

DIRTY FILTERS

 

 

 

the remote control panel to each

75

70

(OPTIONAL)

80

65

85

60

 

55

 

 

90

 

This picture shows a typical photohelic setting. Typical settings are 0.0 in. wg for the lower and 0.10 in. wg for the upper pressure setting. The needle in this photo indicates a negative building pressure. During correct operation, the indicating needle will remain between or near the setting needles.

Pressure Indicating

Pressure Setting

Needle

Needles

Pressure Setting Knobs

Photohelic Gauge

position and confirm that the return

® GREENHECK

 

air damper adjusts accordingly.

2-Position

The damper actuator may take a

Damper Control

few minutes to open or close.

Modulating

Potentiometer Control — a modulating spring return actuator is used to control the return air amounts.

The return air damper modulates

from fully open to fully closed based on a signal from a remote potentiometer.

To test potentiometer operation,

turn the potentiometer to the two 858090 655560 extremes. With 80/20 recirculation,

confirm that the return air damper fully opens and fully closes. When the potentiometer is at 0, the return air damper will open. When the potentiometer is at 100, the return air damper will close. The damper

actuator may take a few minutes to open or close.

20Model VSU Make-Up Air

External Signal — a modulating spring return actuator is used to control the return air amounts. Return air damper modulates from fully open to fully closed based on an external 2-10 VDC or 4-20 mA signal (by others).

The return air damper will close with a 10 VDC or 20 mA signal. The return air damper should open with a 2 VDC or 4mA signal. The damper actuator may take a few minutes to open or close.

Operation - Electrical

Electrical Sequence

1.Exhaust Fan Contact (S1) Closed (optional)

Power passes to N.C. exhaust overload contact

(ST2 OL) (optional)

Power passes to exhaust starter(s) ST2

N.O. exhaust starter switches are energized and closed

Power passes to exhaust fans

Exhaust fan(s) (M2) start

2.Supply Fan Contact (S2) Closed

Power passes through N.C. field supplied fire contact (FSC)

Power passes through N.O. exhaust fan contact

(ST2), which is closed when the exhaust relay (ST2) is activated (optional)

®

Page 20
Image 20
Greenheck Fan 470654 manual Operation Recirculating Units optional, Operation Electrical, Recirculation Operation

470654 specifications

Greenheck Fan 470654 is a cutting-edge ventilation solution designed to meet the demanding requirements of commercial and industrial applications. Renowned for its reliability and efficiency, this fan model integrates advanced technologies and engineering to provide optimal air movement and control.

One of the standout features of the Greenheck Fan 470654 is its robust construction. Designed with high-quality materials, the fan promotes longevity and durability, making it suitable for use in tough environments. This fan features a heavy-gauge steel housing that minimizes vibration and enhances noise reduction, contributing to a quieter operation, a critical factor in maintaining a serene working environment.

The fan is equipped with a powerful motor that ensures efficient airflow, achieving high performance while consuming minimal energy. This energy efficiency is emphasized through the use of advanced motor technology, including variable frequency drive (VFD) compatibility. VFDs allow for precise control of the fan speed, enabling adjustments based on system demand, thus significantly reducing energy consumption and operating costs.

In terms of airflow performance, the Greenheck Fan 470654 is engineered to provide a high volume of air movement while maintaining static pressure. Its aerodynamic design minimizes resistance, enhancing overall efficiency. The fan is designed to operate across a range of static pressures, making it versatile for different applications, from commercial kitchens to large manufacturing facilities.

Additionally, the fan's installation is straightforward, thanks to its user-centric design. The model incorporates mounting brackets and options for various duct configurations, ensuring seamless integration into existing systems. Maintenance is also made easier with accessible components, allowing technicians to perform regular checks and upkeep without extensive downtime.

Safety features are a priority in the design of the Greenheck Fan 470654. It includes protective features such as thermal overload protection to prevent motor damage and extend operational life. The fan's design also adheres to industry standards and regulations, providing peace of mind for users.

In summary, the Greenheck Fan 470654 is a well-engineered solution that combines durability, efficiency, and advanced technology to deliver superior performance in ventilation applications. With its powerful motor, energy-saving capabilities, and ease of installation and maintenance, it stands out as a reliable choice for professionals seeking optimal airflow management.