![](/images/new-backgrounds/1010201/1020147x1.webp)
Troubleshooting
Insufficient Airflow
Damper(s) not fully opened?
No
System static losses too high?
No
Blower speed too low?
No
Filters dirty or clogged
No
Leaks in ductwork
No
Belt slipping
Yes
Everything is working properly,
consult factory.
Too Much Airflow
Blower speed too high?
No
Filters not in place?
No
Insufficient external
static pressure?
No
Everything is working properly,
consult factory.
24Model VSU
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Adjust damper linkage(s), or replace faulty actuator(s).
Damper actuators may take a few minutes to open.
Reduce losses by improving ductwork.
Adjust drives as needed.
Reference:
Clean or replace filters.
Reference: Maintenance - Routine, Filters, pg. 31
Repair leaks.
Replace or tighten belt.
Reference: Maintenance - Routine,
Adjust drives as needed.
Reference:
Install filters.
Increase external static pressure.
®