Operation - VAV Units (optional)

NOTE

Blower Start-Up, as shown on page 14, should be performed before the blower is run.

NOTE

For maintenance issues associated with variable frequency drives, consult the drive’s manual supplied with the unit. The drives are programmed at the factory and should not need any adjustment during installation and start-up. For kitchen applications, the drive may be located in the kitchen or in the unit.

Variable Volume Operation

The variable volume option is recommended when a building’s exhaust volume may vary. This option enables the make-up air volume to track with the exhaust volume, providing only the amount of make- up air required. Control strategies include 2-speed and modulating blowers. Before the unit is left in service, the variable volume control system should be tested.

2-Speed

A variable frequency drive (VFD) is used to control air volumes. The VFD can be switched to low or high speed from a remote control panel. Turn the fan speed switch on the remote control panel to each position and confirm that the fan speed adjusts accordingly.

Modulating

Potentiometer Control — a variable frequency drive is controlled by input from a remote

speed selector (potentiometer). This

EXHAUST

(OPTIONAL)

unit allows easy manual adjustment

SUPPLY

MAIN VALVES

HEAT

of make-up air volumes. To test

 

BLOWER

Building Pressure Control —

SUPPLY

BLOWER

a variable frequency drive is

 

 

EXHAUST

 

controlled according to input from

 

(OPTIONAL)

 

 

MAIN VALVES

 

HEAT

 

 

a pressure sensing device.

 

 

 

Turn both knobs to the upper

75 70

 

DIRTY FILTERS

most pressure setting. You may

80

65

(OPTIONAL)

 

85

60

 

90

55

 

have to remove the outdoor

 

 

 

pressure tap tubing. VAV systems

 

 

PHOTOHELIC

should go to maximum speed. Set

 

 

 

both knobs at the lowest setting

 

 

GREENHECK

and the VAV systems should go to

With Maxitrol 44 Room Thermostat

 

minimum speed.

Building

Pressure Control

 

Reset the correct pressure limits

 

 

 

before starting the unit.

 

 

 

Pressure Indicating

 

Pressure Setting

This picture depicts a typical

Needle

 

Needles

 

 

photohelic setting. Typical

 

 

 

settings are 0.0 in. wg for

 

 

 

the lower pressure setting

 

 

 

and 0.10 in. wg for the upper

 

 

 

pressure setting. The needle

 

 

 

indicates a negative building

 

 

 

pressure. During correct

 

 

 

operation, the indicating

 

 

 

needle will remain between or

Pressure Setting Knobs

near the setting needles.

Photohelic Gauge

External Signal — a variable frequency drive is controlled according to input from an external 2-10 VDC or 4-20 mA signal (by others).

A 2 VDC or 4 mA signal will send the blower to low speed. The blower will go to maximum speed with a 10 VDC or 20 mA signal.

Variable Kitchen Control — A variable frequency drive is controlled by input from a remote speed control. This unit allows automatic adjustment of make-up air volumes based on varying cooking loads.

Burner Bypass Damper (optional)

The self-adjusting burner bypass damper is a device

potentiometer operation, turn the

 

 

DIRTY FILTERS

potentiometer to the two extremes.

 

 

75

70

 

65

(OPTIONAL)

80

60

With variable volume, make sure the fan goes to maximum and minimum speed.

When the potentiometer is at 0, the fan speed will be at its minimum. When the potentiometer is at 100, the fan will be at its maximum speed.

used in variable volume units. Its function is to maintain proper combustion by providing a constant airflow over the burner when outside air volumes are changed. It is located underneath the burner as shown in the picture.

Burner

Bypass Damper

Burner Bypass Damper

warning

The burner bypass damper is set-up at the factory. The weights should not be adjusted in the field. The damper may not fully close during minimum outside air mode.

Model VSU Make-Up Air 19

®