Greenheck Fan 474118 installation manual Table of Contents, Unit Identification

Models: 474118

1 12
Download 12 pages 54.91 Kb
Page 3
Image 3

Removing from Storage

As fans are removed from storage to be installed in their final location, they should be protected and maintained in a similar fashion, until the fan equipment goes into operation.

Prior to assembly and installation of the Vektor fan and system components, inspect the fan assembly to make sure it is in working order.

1.Check all fasteners, set screws on the fan, wheel, bearings, drive, motor base and accessories for tightness.

2.Rotate the fan wheel(s) by hand and assure no parts are rubbing. Access to the wheel is obtained through a bolted panel located on the side of the fan housing.

Table of Contents

Receiving, Handling, Storage

. . . . . . .

2

Unit Identification

. . . . . . . . . .

. . 3

Installation

 

 

Plenum Cabinet

 

4

Unit Weights . . . . . . . . . . . . . . . . 4

Plenum Service Clearances and Access

. . 5

Assembly and Installation

 

 

Roof Curb and Plenum Cabinet. .

. . . . .

5-6

Duct Connections

 

 

Plenum Inlet

 

7

Duct Connections

7

Drain Trap

 

8

Coils

Water Coil . . . . . . . . . . . . . . . . 8-9

Coil Checklist

. 9

Filter Replacement

. . 9

Coating Touch-Up Procedure

. 10

Optional Accessories

 

Dirty Filter Sensor (Magnehelic Gauge)

10

Vapor Tight Lights

10

Routine Maintenance

 

Coils

11

Filters. .

. . . . . . . . . . . . . . . .

11

Drain Pan.. . . . . . . . . . . . . . . . 11

Service

 

 

Coil Replacement

12

Reference

 

 

Maintenance Log

12

Warranty

. 12

Unit Identification

System Identification Tags

The tag shown is an example of an identification label on the fan. The information provides general details about the fan, as well as containing specific information unique to the unit. When contacting your Greenheck representative with future needs or questions, please have the information on this label available. Tags

are mounted in an area which is clearly visible,

usually on the side of the fan cabinet.

ERS and Vektor fan systems may arrive in component pieces due to shipping restrictions. Individual components of a system have matching identification tags which should be used to identify and assemble the complete system. Assembling systems with different identification tags can cause reductions in the fan(s) performance.

General Information

To ensure a successful installation, the instructions in this manual should be read and adhered to. Failure to comply with proper installation procedures may void the warranty.

Pre-Installation Checks

Prior to fully assembling and installing the ERS plenum cabinet and Vektor fan bypass plenum components, inspect plenums, coils, and fan assembly to make sure they are in working order.

Storage

When an ERS plenum cabinet is not going to be in service for an extended period of time, certain procedures should be followed to keep the plenum and coils in proper operating condition. Cover unit with tarp to protect from dirt and moisture.

NOTE

Do not use a black tarp as this will promote condensation.

ERS

Plenum

Cabinet

Fan Bypass

Air Plenum

(BAP)

Fan System Components

Vektor ERS-MD Energy Recovery Plenum Laboratory Exhaust 3

Page 3
Image 3
Greenheck Fan 474118 installation manual Table of Contents, Unit Identification