Greenheck Fan 47555 specifications Installation, Removing From Storage, System Identification Tags

Models: 47555

1 16
Download 16 pages 16.1 Kb
Page 3
Image 3
REMOVING FROM STORAGE

REMOVING FROM STORAGE

As fans are removed from storage to be installed in their final location, they should be protected and maintained in a similar fashion, until the fan equipment goes into operation.

Prior to assembly and installation of the Vektor fan and system components, inspect the fan assembly to make sure it is in working order.

1.Check all fasteners, set screws on the fan, wheel, bearings, drive, motor base and accessories for tightness.

2.Rotate the fan wheel(s) by hand and assure no parts are rubbing. Access to the wheel is obtained through a bolted panel located on the side of the fan housing.

3.Ensure proper wheel settings for radial gap and alignment. Refer to page 13.

Installation

Installations with inlet or discharge configurations that deviate from this standard may result in reduced fan performance. Restricted or unstable flow at the fan inlet can cause pre-rotation of incoming air or uneven loading of the fan wheel yielding large system losses and increased sound levels.

System Identification Tags

Vektor fan systems may arrive in component pieces due to shipping restrictions. Individual components of a system have matching identification tags which should be used to identify and assemble the complete system.

Assembling systems with different identification tags

can cause reductions in the fan(s) performance.

Standard Fan Configurations

The following illustration identifies a typcial configuration of the Vektor-CD system. Greenheck also supplies custom configurations. Your system may not be depicted in the drawing shown. Refer to submittal drawing.

 

WINDBAND

FLEX CONNECTOR

 

 

 

 

ISOLATION

 

NOZZLE

DAMPER

 

 

 

PLENUM

 

 

 

 

FAN

 

 

 

FH

 

 

FW

 

FL

 

 

 

OPTIONAL

 

 

CURB SQR

 

 

ROOF CURB

 

 

PRIMARY INLET

 

 

 

 

ISOLATOR

 

 

Vektor-CD Arrangements

 

Vektor-CD

 

 

Vektor-CD

Single Fan System

Opposed Fan System

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Vektor-CD

Vektor-CD

Dual Fan System

Triple Fan System

Rigging / Assembly Instructions

1.Use standard lifting and rigging practices.

2.All lifting lugs on each component must be utilized at the same time.

3.Plenum, blower, and windband are to be kept level during installation.

 

Chains

 

Spreader Bar

 

Chains

Lifting

Lifting

Lugs

Lugs

Gasketing

Bypass Air

 

Plenum

 

Roof Curb / Structural Support



Vektor-CD Centrifugal Laboratory Exhaust

Vektor-CD Centrifugal Laboratory Exhaust

®

Page 3
Image 3
Greenheck Fan 47555 Installation, Removing From Storage, System Identification Tags, Standard Fan Configurations