Greenheck Fan 47555 Fan Installation, Fan Housing Installation, Fan Stack Installation

Models: 47555

1 16
Download 16 pages 16.1 Kb
Page 7
Image 7
Fan Installation

Fan Installation

Fan Housing Installation

Lines of attachment are to be lifted in the vertical direction to prevent damage. Spreader bars

are recommended.

Fan Housing Installation Lifting lugs located on the four corners of the base

If the windband is shipped attached to the fan housing or if the windband is secured to the fan housing prior to mounting to the plenum, the fan / windband assembly should be lifted by the lifting lugs located on the fan housing. Do not lift this assembly by the lifting lugs located on the windband. Connect fan to plenum using Excelon™ flex connector found in the Vektor-CD hardware kit.

Fan Stack Installation

**Guy wire attachments Fan Stack Installation

Stack Extension Windband Installation

Fan Assembly

If fan requires a stack or stack extension, install on fan before installing nozzle and windband. Place gasketing between any sections, blower housing and initial stack. Use lifting lugs to position each piece into place. Attach stack or stack extension to blower housing using 316 stainless steel bolts (provided) through flanges aligning bolt patterns. Use anti- seize gel (provided) to prevent galling/welding of all stainless steel fasteners.

Greenheck strongly recommends the use of guy wires on any system that incorporates the usage of a stack extension including inline attenuators. Subsequent guy wires are to be designed and installed by others.

Windband Installation

Using the windband

 

lifting lugs, place

Four (4) lifting

windband over blower

lugs located

 

at top of

discharge, aligning

windband

windband support

 

bracket holes with

 

bolt holes in blower

 

housing. Attach

 

windband to blower

 

discharge using 316

 

stainless steel bolts

 

(provided) through support brackets welded to the inside of the windband. Use anti-seize gel (provided) to prevent galling / welding of all stainless steel fasteners.

Bypass Air Plenum Installation

Span determines the number of lifting lugs to be used during installation:

Lifting lugs located at top

Span

of bypass air plenum

 

Span

No. of Lifting Lugs

 

 

12 inches or less

Minimum of 4 lifting lugs

 

 

12 to 18 inches

Minimum of 6 lifting lugs

 

 

18 inches or greater

Minimum of 8 lifting lugs

 

 

Guy Wire Locations

1-1/4 inch thru-hole typical

NOTE: Guy wires to be supplied by others. Fastening to building structure to be provided and engineered by others.

If your fan requires stack extensions, the use of guy wires is recommended. See drawing for guy wire connection locations.

Note: Keep 36 inches minimum spacing around unit to provide adequate clearance for servicing or repairing unit.

®

Vektor-CD Centrifugal Laboratory ExhaustBypass Air Plenum Installation

Page 7
Image 7