For Vektor Fans without a Weatherhood
A guard / cover is located on the side of the plenum section. Removal of the guard / cover gains access to the damper linkages, actuator (optional from factory) and transformer (optional from factor). The entire bypass damper assembly can be removed through this opening. The isolation damper assembly can be removed from its location by unbolting the frame from the plenum and removing the flex connector.
If the Vektor units were not supplied with optional actuators, the dampers have an extended jackshaft for field mounting a customer supplied actuator.
Motor Disconnect Wiring & Isolation Damper Wiring Diagram
LINE IN
208/230/460/575 V
3 PHASE
DISCONNECT
208/230/460/575 V
3 PHASE
MOTOR 208/230/460/575/60/3
Disconnect is mounted to fan housing. Transformer is mounted to bypass air plenum near isolation damper actuator motor. For systems that ship
OPTIONAL ISOLATION
DAMPER CONTROL
TRANSFORMER
208/230/460/575 V 1 PHASE
24/115 V 1 PHASE
ISOLATION DAMPER
ACTUATOR MOTOR
POWER OPEN/SPRING CLOSE
| NOTE: If a Variable Frequency Drive is used to control fan speed, |
FIELD WIRING | transformer and actuator will not function properly when wired as |
FACTORY WIRING | shown. Transformers must be wired independently from VFD control. |
Applications with Variable Frequency Drives (VFD)
For Vektor systems with
If fan flow (motor speed) is to be controlled using a VFD, the reduced voltage and frequency supplied to the fan will cause control problems with the isolation damper actuator.
When a Vektor control sequence requires the use of a VFD, it is suggested that the control contractor supply the isolation damper actuator voltage — independent of the power supplied to the Vektor fan motor.
Isolation Damper Control
Isolation dampers on
®