Unit Start-Up

Refer to Parts List section for component locations.

Fans

The ERVe models contain

two forward curved (supply &

exhaust) fans. These forward

curved fans should be checked

for free rotation. If any binding

5.Place belts over sheaves. Do not pry or force belts, as this could result in damage to the cords in the belts.

6.With the fan off, adjust the belt tension by moving the motor base. (See belt tensioning procedures in the Routine Maintenance section of this manual).

When in operation, the tight side of the belts should be in a straight line from sheave to sheave with a slight bow on the slack side.

occurs, check for concealed

 

damage and foreign objects

 

in the fan housing. Be sure to

Forward Curved

check the belt drives per the

Exhaust Fan

start-up recommendations in

 

the following section.

 

CAUTION

WRONG

WRONG

WRONGCORRECT

When operating conditions of the fan are to be changed (speed, pressure, temperature, etc.), consult Greenheck to determine if the unit can operate safely at the new conditions.

Fan Performance Modifications

Due to job specification revisions, it may be necessary to adjust or change the sheave or pulley to obtain the desired airflow at the time of installation. Start-up technician must check blower amperage

to ensure that the amperage listed on the motor nameplate is not exceeded. Amperage to be tested with access doors closed and ductwork installed.

Fan Belt Drives

The fan belt drive components, when supplied by Greenheck, have been carefully selected for the unit’s specific operating condition. Utilizing different components than those supplied could result in unsafe operating conditions which may cause personal injury or failure of the following components:

• Fan Shaft

• Bearings

• Motor

• Fan Wheel

• Belt

 

Tighten all fasteners and set screws securely and realign drive pulleys after adjustment. Check pulleys and belts for proper alignment to avoid unnecessary belt wear, noise, vibration and power loss. Motor and drive shafts must be parallel and pulleys in line (see diagrams in this section).

Belt Drive Installation

1.Remove the protective coating from the end of the fan shaft and assure that it is free of nicks and burrs.

2.Check fan and motor shafts for parallel and angular alignment.

3. Slide sheaves on shafts. Do not drive sheaves on as this may result in bearing damage.

4. Align fan and motor sheaves with a straight-edge or string and tighten.

Direction of Fan Wheel Rotation

Blower access is labeled on unit. Check for proper wheel rotation by momentarily energizing the fan. Rotation is determined by viewing the wheel from the drive side and should match the rotation decal affixed to the fan housing (see Rotation Direction figures).

If the wheel is rotating the wrong way, direction can be reversed by interchanging any two of the three electrical leads. Check for unusual noise, vibration, or overheating of bearings. Refer to the Troubleshooting section of this manual if a problem develops.

otatio

n

R

 

n

 

 

 

io

 

 

 

 

 

a

t

 

Airflow

 

 

t

 

 

 

o

 

 

 

R

 

 

 

Forward Curved

Fan RPM

Supply fan and exhaust fan will have an adjustable motor pulley (on 15 HP and below) preset at the factory to the customer specified RPM. Fan speed can be increased or decreased by adjusting the pitch diameter of the motor pulley. Multigroove variable pitch pulleys must be adjusted an equal number

of turns open or closed. Any increase in fan speed represents a substantial increase in load on the motor. Always check the motor amperage reading and compare it to the amperage rating shown on the motor nameplate when changing fan RPM. All access doors must be installed except the control center door. Do not operate units with access doors open or without proper ductwork in place as the fan motors will overload.

Model ERVe Energy Recovery Unit 21

Page 21
Image 21
Greenheck Fan ERVe manual Unit Start-Up

ERVe specifications

The Greenheck Fan ERVe series stands at the forefront of energy-efficient ventilation solutions, specifically designed to meet the growing demands for energy conservation and enhanced indoor air quality in commercial buildings. As part of Greenheck's commitment to innovation, the ERVe series offers a variety of models tailored to diverse applications, including schools, hospitals, and office buildings.

One of the key features of the ERVe series is its advanced energy recovery technology. The ERVe utilizes a heat recovery wheel that efficiently transfers heat and moisture between the exhaust and incoming airstreams. This process significantly reduces heating and cooling loads on HVAC systems, promoting energy savings and improving overall system efficiency. By reclaiming energy that would otherwise be wasted, the ERVe ensures that buildings not only conform to energy codes but also contribute to sustainability goals.

The ERVe series is designed with versatility in mind. It offers multiple configurations, including vertical and horizontal orientations, which makes it adaptable to various installation environments. Additionally, the unit can be equipped with a range of options such as pre-filters, post-filters, and variable speed drive motors, allowing for customization based on specific application needs. This adaptability ensures that the ERVe can meet the specific air quality requirements of different spaces while maintaining optimal airflow.

Another significant characteristic of the ERVe series is its low noise operation. The design incorporates advanced acoustical features, including sound attenuators and insulated panels, which minimize sound transmission and enhance occupant comfort. As noise control becomes increasingly important in settings like educational institutions and healthcare facilities, the ERVe series excels in providing a peaceful indoor environment.

Moreover, the ERVe series is engineered with durability in mind. Constructed from high-quality materials, the units are built to withstand the rigors of continuous operation. The robust design not only extends the service life of the equipment but also reduces maintenance requirements, leading to lower overall operational costs.

In terms of control and monitoring, the ERVe series is compatible with various building management systems, allowing for integration into sophisticated HVAC controls. This feature enables real-time data tracking and optimization, enhancing the efficiency of indoor climate management.

Overall, the Greenheck Fan ERVe series represents a significant advancement in ventilation technology, combining energy efficiency, customizable features, low noise operation, and durability. These characteristics ensure that the ERVe is a reliable choice for modern commercial buildings striving for improved air quality and reduced energy consumption.