Rail Mounting / Layout
•Rails designed to handle the weight of the ERVe should be positioned as shown on the diagram (rails by others).
•Make sure that rail positioning does not interfere with the supply air discharge opening or the exhaust air intake opening on the ERVe unit. Avoid area dimensioned “B” below.
•Rails should extend beyond the unit a minimum of 12 inches on each side.
•Set unit on rails.
Service Clearances
ERVe units require minimum clearances to perform routine maintenance, such as filter replacement, energy wheel cassette inspection, and fan belt adjustment. Blower and motor assemblies, energy recovery wheel cassette and filter sections are always
provided with a service door |
|
|
| |
or panel for proper |
|
|
|
|
component |
| C | B | CLEARANCE |
access. |
|
|
| |
D |
|
|
| A |
CLEARANCE |
|
|
| |
D |
|
|
|
Isometric view of
ERVe on rails
B | A |
Side view of
ERVe on rails
Unit Size | A | B |
|
|
|
5.75 | 18 | |
|
|
|
5.75 | 20.5 | |
|
|
|
6 | 22.5 | |
|
|
|
6 | 26 | |
|
|
|
All dimensions are in inches.
Recommended Service Clearances
Unit Size | A | B | C | D |
|
|
|
|
|
24 | 24 | 42 | 35 | |
|
|
|
|
|
32 | 24 | 48 | 43 | |
|
|
|
|
|
32 | 24 | 54 | 43 | |
|
|
|
|
|
32 | 24 | 60 | 44 | |
|
|
|
|
|
All dimensions are in inches.
Access Panel Description and Location
3
4
5 | 2 |
|
1
Outdoor air filters
Frost control
1Outdoor air sensors Preheater and controls Outdoor air intake damper
2Supply blower and motor
3Electric control center Main disconnect Energy wheel cassette
4Exhaust air filters Exhaust air intake damper
5Exhaust blower and motor Outdoor air intake damper actuator
6Model ERVe Energy Recovery Unit