Roof Curb Mounting

Roof Curb Mounting

Roof curb details including duct location dimensions, are available on Roof Curb Assembly Instructions, Part Number 472119.

Rooftop units require curbs to be mounted first. The duct connections must be located so they will be clear of structural members of the building.

1.Factory Supplied Roof Curbs: Roof curbs are Model GKD. The GKD ships in a knockdown kit (includes duct adapter) and requires field assembly (by others). Assembly instructions are included with the GKD curbs.

2.Install Curb: Locate curb over roof opening and fasten in place. (Refer to Recommended Roof Openings). Check that the diagonal dimensions are within ±1/8 inch of each other and adjust as necessary. For proper unit operation, it is important that the installation be level. Shim as required to level.

3.Install Ductwork: Installation of all ducts should be done in accordance with SMACNA and AMCA guidelines. Duct adapter provided to support ducts prior to setting the unit.

4.Install Insulation: One-inch deep insulation pans were provided with the curb assembly. Install insulation prior to setting the unit.

Insulation is not included from the factory.

5.Set the Unit: Lift unit to a point directly above the curb and duct openings. Guide unit while lowering to align with duct openings. Roof curbs fit inside the unit base. Make sure the unit is properly seated on the curb and is level.

Curb Outside Dimensions and Weights

Curb Outside Dimensions - continued

Unit Side

1.895

Unit Base

 

4.844

 

 

Insulation Pan

 

 

(Insulation not included)

Roof Curb

Curb Outside Dimensions and Weights1.549 Curb Outside Dimensions - continued

Ductwork Connections 0.775

Curb Cap Details for Factory Supplied Roof Curbs

Ductwork Connections

Examples of poor and good fan-to-duct connections are shown below. Airflow out of the fan

should be directed straight or curve

the same direction as

 

 

 

 

the fan wheel rotates.

 

 

 

tion

 

 

 

 

 

 

a

 

 

 

 

 

t

 

Poor duct installation

R

o

 

 

 

 

 

 

 

 

 

will result in low airflow

 

 

 

and other system

 

 

 

POOR

effects.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

tion

Length of Straight Duct

 

 

a

 

t

 

R

o

 

 

 

 

 

 

 

 

 

 

 

 

 

GOOD

W

L

W

L

WF

LF

 

 

 

Unit Size

L

W

LF

WF

Curb Weight

(lbs.)

 

 

 

 

 

 

 

 

 

 

 

ERVe-20

61.125

40.375

64.875

44.125

93

 

 

 

 

 

 

ERVe-35

63.375

48.5

67.125

52.25

106

 

 

 

 

 

 

ERVe-45

67.375

55.5

71.125

59.25

120

 

 

 

 

 

 

ERVe-55

78.25

65.5

82

69.188

148

 

 

 

 

 

 

All dimensions are in inches. Weights are for 14-inch high GKD type curbs.

Recommended Discharge Duct Size and Length

Model

Blower Size

Duct Size

Straight Duct Length

 

 

 

 

ERVe-20

9

14 x 14

36

 

 

 

 

ERVe-35

10

20 x 20

36

 

 

 

 

ERVe-45

12

20 x 20

36

 

 

 

 

ERVe-55

15

28 x 28

60

 

 

 

 

All dimensions shown in inches.

Recommended duct sizes are based on velocities across the cfm range of each model at approximately 800 feet per minute (FPM) at minimum airflow and up to 1600 fpm at maximum airflow. Recommended duct sizes are only intended to be a guide and may not satisfy the requirements of the project. Refer to plans for appropriate job specific duct size and/or velocity limitations.

Straight duct lengths were calculated based on 100% effective duct length requirements as prescribed in AMCA Publication 201. Calculated values have been rounded up to nearest foot.