Greenheck Fan TCB installation instructions Installation Practices

Models: TCB

1 2
Download 2 pages 26.83 Kb
Page 1
Image 1
READ AND SAVE THESE INSTRUCTIONS

PN 464115

READ AND SAVE THESE INSTRUCTIONS

Supplement for Model TCB with UL-762

®

Installation Operation and Maintenance Manual

Supplement for UL-762 Listed (Restaurant Exhaust) Fans

This supplement to the TCB Installation Operation and Maintenance Manual is intended to provide additional information when dealing with fans used in applications involving grease laden air. Refer to the TCB Installation, Operation and Maintenance Manual (PN 456557) for items that are not specifically addressed (handling, storage, start-up, troubleshooting and maintenance) in this supplement.

Installation Practices

All units used in applications with grease laden air are to be installed in accordance to NFPA 96, IMC 2203 and local codes. Consult local code authorities for your specific requirements.

Fans shall be located in an easily accessible area of adequate size to allow for service or removal. Exhaust fans with ductwork connected to both ends shall have access for cleaning and inspection within 3 ft (0.92 m) of each end of the fan (NFPA 96).

Maintain a minimum clearance of at least 18 inches (457 mm) to combustible material and 6 inches (125.4 mm) to either limited-combustible or noncombustible material (NFPA 96).

Fans are to be installed with the motors in the 3 or 9 o’clock (C or G) positions. Motors located in this configuration may cause an unbalanced load that should be considered if isolators are to be used. Equalized loading between isolators can be achieved through the use of mounting rails. Refer to the TCB IOM for details and installation instructions involving mounting rails.

It is recommended to install the fan near the end of the duct run. This limits the amount of positive pressure in the system. The diagram below illustrates an inline fan exhausting air near the final termination point. See local codes and NFPA 96 for any restrictions and requirements for wall terminations.

Airflow

Fan

Minimum duct at discharge

Exhaust air exiting the building

Exterior Wall

A drain is provided for single-point drainage of water and residue. When installed correctly, one of the two housing drains will be located on the bottom. This drain is used to remove any accumulated grease and / or cleaning solutions. Some means for collection of this residue must be provided, either a container directly under the drain or use an adapter and pipe to carry the residue to a remote collection point. Remove drain plug prior to connection to grease collection device.

Provision to open and remove the access door is required for periodic cleaning and maintenance. The access door is clearly labeled and indicates that access to this location must be maintained. Any enclosure openings required to reach the access panel shall be large enough to allow for the removal of the panel.

Page 1
Image 1
Greenheck Fan TCB installation instructions Installation Practices, Read And Save These Instructions