SECTION 2: POWER SUPPLY

SECTION 2: POWER SUPPLY

Availability

Before installing the machine, consider the avail- ability and proximity of the required power supply circuit. If an existing circuit does not meet the requirements for this machine, a new circuit must be installed. To minimize the risk of electrocu- tion, fire, or equipment damage, installation work and electrical wiring must be done by a qualified electrician in accordance with all applicable codes and standards.

Electrocution, fire, or equipment damage may occur if machine is not correctly grounded and connected to the power supply.

Full-Load Current Rating

The full-load current rating is the amperage a machine draws at 100% of the rated output power. On machines with multiple motors, this is the amperage drawn by the largest motor or sum of all motors and electrical devices that might operate at one time during normal operations.

Full-Load Current Rating at 110V

14

Amps

Full-Load Current Rating at 220V

7

Amps

The full-load current is not the maximum amount of amps that the machine will draw. If the machine is overloaded, it will draw additional amps beyond the full-load rating.

If the machine is overloaded for a sufficient length of time, damage, overheating, or fire may result— especially if connected to an undersized circuit. To reduce the risk of these hazards, avoid over- loading the machine during operation and make sure it is connected to a power supply circuit that meets the requirements in the following section.

-8-

Circuit Information

A power supply circuit includes all electrical equip- ment between the main breaker box or fuse panel in your building and the incoming power connec- tions at the machine. This circuit must be sized to safely handle the full-load current drawn from the machine for an extended period of time.

For your own safety and protection of property, consult a qualified electrician if you are unsure about wiring practices or electrical codes in your area.

Note: The circuit requirements listed in this man- ual apply to a dedicated circuit—where only one machine will be running at a time. If this machine will be connected to a shared circuit where mul- tiple machines will be running at the same time, consult a qualified electrician to ensure that the circuit is properly sized for safe operation.

Circuit Requirements for 110V

This machine is prewired to operate on a 110V power supply circuit that has a verified ground and meets the following requirements:

Nominal Voltage

110V/120V

Cycle

60 Hz

Phase

Single-Phase

Circuit Rating

15 Amps

Plug/Receptacle

NEMA 5-15

Circuit Requirements for 220V

This machine can be converted to operate on a 220V power supply. To do this, follow the Voltage Conversion instructions later in this section. The intended 220V circuit must have a verified ground and meet the requirements that follow:

Nominal Voltage

220V/240V

Cycle

60 Hz

Phase

Single-Phase

Circuit Rating

15 Amps

Plug/Receptacle

NEMA 6-15

Model G0710 Dust Collector (Mfg. since 6/10+)