![Figure 3 F](/images/new-backgrounds/54872/548729x1.webp)
SPRING
REDUCER
H
Figure 3 E - Pull the 3 1/8” and 6” Corrugated Pipe Toward the Water Heater Individually.
1.Pull the 3 1/8” corrugated pipe toward the water heater and leave some length over the water heater’s center for bending.
2.Pull the 6” corrugated pipe toward the water heater and leave it 1” shorter than 3 1/8” pipe.
3.Make sure there are two springs evenly spaced at the bend in the pipe.
4.Use metal hangers to keep vent pipe level or with a slope upward from the heater to terminal.
Figure 3 F
Bend the 3 1/8” and 6” corrugated pipe all together toward the water heater’s flue connection.
Figure 3 G
Pull and connect the 3 1/8” corrugated pipe to the water heater’s flue tube reducer with
*The sealant between 3 1/8” corrugated pipe and water heater’s flue tube reducer must be
Figure 3 H
Apply silicone around 6” collar on air manifold box. Pull corrugated vent tube all the way on to collar and secure with one sheet metal screw (approx. 3/4”) up from edge of vent tube. Pull gear clamp past screw and tighten.
SLOPE
Figure 3 J
Check the vent pipe’s level or slope again, and adjust if required.
Offset vent pipe Arrangement
TOP VIEW
90°
MAXIMUM
BEND
Figure 3 K - CONDITION 1
Where a straight vent pipe arrangement is impossible, a horizontal 90 degree maximum bend can be made. Use the water heater casing outer diameter as a template to form the corrugated pipe.
– 4 –