Installation of Indoor Unit

ELECTRICAL REQUIREMENT

Electric wire size and fuse capacity:

Select wire sizes and circuit protection from table below. (This table shows 20 m length wires with less than 2% voltage drop.)

Table 5

Item

 

Circuit

breaker

Power source

Earth leakage breaker

 

 

 

wire size

 

 

 

Phase

Switch breaker

Overcurrent protector

Switch

Leak

Model

(minimum)

 

(A)

rated capacity (A)

(mm2)

breaker(A)

current(mA)

 

 

 

 

 

 

 

For series 282, 362

1

40

26

6.0

40

30

 

 

 

 

 

 

 

For series 282(EAA)

3

30

20

2.5

30

30

362

 

 

 

 

 

 

For series 522, 482,

3

30

20

4.0

30

20

602

 

 

 

 

 

 

Fig. 15

Insulation tube

Cord clamp

Use VW-1, 0.5 to 1.0 mm thick, PVC tube as the insulation tube.

CAUTION

(1)Match the terminal block numbers and connection cord colors with those of the outdoor unit.

Erroneous wiring may cause burning of the electric parts.

(2)Connect the connection cords firmly to the terminal block. Imperfect installation may cause a fire.

(3)Always fasten the outside covering of the connection cord with the cord clamp. (If the insulator is chafed, electric leakage may occur.)

(4)Always connect the ground wire.