Installation Manual For Indoor Unit

11. Refrigerant pipe

[The air side pipe, liquid side pipe must be faithfully heat insulated, if no heat insulation, it may cause water leakage.]

The outdoor unit has been charged with refrigerant.

When connect the pipe to the unit or dismantling the pipe from the unit, please follow the figure shown, use spanner and torque spanner together.

When connect cone nut, the inner side and outside of cone nut should paste with refrigerant oil. Use hand to twist 3-4 rings, then fasten with spanner.

Referring to Table I to confirm the fasten torque. (too tight may damage nut leading to leakage)

Check if the connection pipe leaks, then do heat insulation treatment, as below figure shown. Only use seal cushion to bind the joint part of air pipe and heat insulation parts.

Paste the refrigerant oil here

Torque spanner

Spanner

Pipe joint

Cone nut

Middle size seal cushion (accessory)

(Use seal cushion to bind the pipe joint)

Clamp

Heat insulation (accessory)

(for liquid pipe)

Heat insulation (accessory) Gas pipe (for gas pipe)

Liquid pipe

80

510

 

 

 

Liquid pipe

Gas pipe

Electric box

 

 

 

 

 

 

 

Upper

 

 

Air inlet

 

 

310

Air outlet

 

 

 

 

Drain hose connection mouth

530

Down side

30

 

 

 

 

 

VP25 PVC pipe

 

 

 

 

Specification of pipe

Tighten torque

Cone dimension

 

Cone

(mm)

 

A (mm)

 

 

9.52

3270~3990 N.cm

12.0~12.4

45

2

(333~407 kgf.cm)

 

R0.4~0.8

 

 

 

90

0.5

 

 

 

15.88

6180~7540 N.cm

 

 

A

18.6~19.0

 

 

(630~770 kgf.cm)

 

 

 

 

 

 

19.05

9720~11860 N.cm

22.9~23.3

 

 

(990~1210 kgf.cm)

 

 

 

 

 

 

 

 

20

 

 