Haier AD242AHBEA Installation Manual For Indoor Unit, The operation method of fan controller

Models: AD28NAHBEA AD42NAHBEA AD36NAHBEA AD52NAHBEA AD242AHBEA

1 22
Download 22 pages 1.2 Kb
Page 20
Image 20
10. The operation method of fan controller

Manual background Installation Manual For Indoor Unit

10. The operation method of fan controller

Through the fan controller switch in the electric box, the air volume of this unit can be continuously adjusted.

It is unnecessary to adjust air volume through the duct side wind level (unit outside static adjustment). The air volume set should be in the operation air volume range.

Figure I shows the position of fan controller in the electric box and operation method.

After finishing the electric work, perform test run. According to the main points in Figure II making the chosen switch No. accordant. And confirm if it reaches the needed air volume.

Note:

1)When operating the fan controller, it is possible to touch the electric charging part, so do cut off the power supply.

2)Do not set the dial at the position less than 1.

3)The figure circled in Figure II indicate the capacity number of fan controller. The non-listed capacity number may exceed the permitted operation capacity range, so it is impossible to operate.

4)When delivering from factory, the capacity number of fan controller is set at ìNo.5î.

Rotate this switch

(capacity number setting:

No. 1 ~ No. 8)

Once the fan controller has trouble, this linker can perform emergency assistant control. When this linker is connected to the linker from the PCB, it can operate with total load.

When this linker is connected to the linker from the PCB, through the fan speed adjustment panel to adjust speed.

Figure 1

 

 

 

 

High

 

Condition of standard air volume

 

 

 

 

 

 

 

 

 

Low

(air volume 100Pa)

 

 

 

 

200

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

*

*

*

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

*

*

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

*

 

 

 

 

 

 

 

 

 

 

 

 

 

Example of

 

 

 

 

 

 

 

*

*

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

duct

Pa

150

 

 

 

 

 

 

 

*

 

 

 

 

 

 

*

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

pressure

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

*

 

 

 

 

 

 

 

 

 

*

 

 

 

 

 

 

 

 

 

 

 

 

 

 

static

100

 

 

 

*

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

*

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Outer

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

50

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

26

30

34 35

 

 

 

40

43

 

Lower limit

 

 

 

 

 

 

 

Upper limit

 

 

 

 

 

 

Standard air volume(m3/min)

 

 

Figure 2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Manual background The example of the method of choosing capacity number:

1)If the unit is in high-speed operation, needing take outer static pressure is 180Pa in capacity air volume 34m3/min as working condition point, according to Figure II ìThe characteristic chart of air volumeî, the capacity number of fan controller is No. 2.

2)If the unit is in low speed operation, needing take outer static pressure is 60Pa in capacity air volume 32m3/min as working condition point, according to Figure II ìThe characteristic chart of air volumeî, the capacity number of fan controller is No. 4.

19

Page 20
Image 20
Haier AD242AHBEA, AD52NAHBEA, AD36NAHBEA Installation Manual For Indoor Unit, The operation method of fan controller