Installing the suspension screw:

Use M8 or M10 suspension screws (4,prepared in the field)(when the suspension screw height exceeds 0.9m,M10 size is the only choice).These screws shall be installed as follows with space adapting to air conditioner overall dimensions according to the original building structures.

Wooden structure

A square wood shall be supported by the beams and then set the suspension screws.

New concrete slab

To set with embedded parts,foundation bolts etc.

Square wood Beam

Suspension screw

 

 

Iron reinforcement

 

 

Foundation bolt

Knife embedded part

Guide plate embedded part

Pipe suspension foundation bolt

Original concrete slad

Use hole hinge,hole plunger or hole bolt.

Steel reinforcement structure

Use steel angle or new support steel angle directly.

Hanging bolt

Suspension screw

Support steel angle

Hanging of the indoor unit

Fasten the nut on the suspension screw and then hang the suspension screw in the T slot of the suspension part of the unit.

Aided with a level meter,adjust level of the unit within 5mm2