Haier HDU-18CF03 Allowable pipe length and drop Pipe material and size, Supplementary refrigerant

Models: HDU-28CF03 HDU-18CF03 HDU-18HF03

1 34
Download 34 pages 49.21 Kb
Page 31
Image 31

Installation Manual For Indoor Unit

! Caution

In installation, if there is refrigerant gas leakage, please take ventilation measures immediately. The refrigerant gas will generate poisonous gas upon contacting fire.

After installation, please verify that there is no refrigerant leakage. The leaked refrigerant gas will produce poisonous gas when meeting fire source such as heater and furnace etc.

Allowable pipe length and drop

These parameters differ according to the outdoor unit. See the instruction manual attached with the outdoor unit for details.

Pipe material and size

Pipe material

Phosphorus deoxidized copper seamless pipe (TP2) for air conditioner

 

 

 

 

 

Gas side

ÿ12.70

HDU-18CF03

Pipe size

Liquid side

ÿ6.35

HDU-18HF03

(mm)

 

 

 

Gas side

ÿ15.88

HDU-28CF03

 

 

Liquid side

ÿ9.52

HDU-28HF03

Supplementary refrigerant

The refrigerant supplementation shall be as specified in the installation instructions attached with the outdoor unit R22

The adding procedure shall be aided with a measuring meter for a specified amount of supplemented refrigerant.

Requirement

Overfilling or underfilling of refrigerant will cause compressor fault. The amount of the added refrigerant shall be as specified in the instructions.

Connection of refrigerant pipe

Conduct flared connection work to connect all refrigerant pipes.

The connection of indoor unit pipes must use double spanners. The installing torque shall be as given in the following table.

Connecting pipe

Installing torque

O.D.(mm)

(N-m)

ÿ6.35

11.8 (1.2kgf-m)

ÿ12.70

49.0 (5.0 kgf-m)

ÿ9.52

24.5 (2.5kgf-m)

ÿ15.88

78.4 (8.0 kgf-m)

 

 

Double-spanner operation

30

Page 31
Image 31