| Exception F200 Wood Insert |
Warning: Do notinstall in sleeping room. |
| Floor Protection | ||
|
|
| In all installations, the area under and around the | |
|
|
| insert must be protected from falling ash and live coals. | |
|
|
| This protector must be of noncombustible material, and | |
|
|
| positioned as shown in the accompanying illustration. | |
|
|
| The guidelines for the floor protection are in both | |
|
|
| USA and CANADA: 8"(200mm) to each side of the door | |
|
|
| opening, and: |
|
|
|
| In USA: | 16" of |
8" | 16"USA |
|
| of the door opening. |
|
|
|
| |
| 18"Canada | Wall | In CANADA: (1) If the floor surface is 0" - 4 1/2"(114 | |
|
| |||
|
|
| ||
Floor Protector |
|
|
| mm) below the insert base, 18"(450mm) |
22" |
|
| of 1/2"(12.7mm) thick, k=.84 thermal | |
|
|
| protection is required in front of the door | |
| 559mm |
|
| opening. |
|
|
|
| (2) If the floor surface is greater than 4 |
|
|
|
| 1/2"(114mm) below the base of the |
|
|
|
| insert, 18"(450mm) of |
|
|
|
| material in front of the door is required. |
|
|
|
| See appendix A. |
Mantel | Clearances |
|
|
| |
| Clearance is the empty space required between the | |
| insert and the nearest combustible surface or object, such | |
2 4" ( 61 0 mm ) as walls, ceilings, floors, or furniture. Clearance distances | ||
with hood | may only be reduced by using methods approved by ei- | |
36" (900 mm) | ||
without hood | ther the CAN/CSA B365 standard (Canada) or NFPA | |
| 211 (U.S.) Contact your building authority for informa- | |
| tion if you are interested in reducing clearance distances | |
| other than those presented here. |
|
| From the front of the insert, clearance to combus- | |
| tible materials such as furniture, curtains, fuel, etc., is: | |
| 48"(1215 mm) in the U.S. and | 60" |
| (1525 mm) in Canada. |
|
| The clearance to combustibles from the top of the | |
| unit to the mantel must be 24" (610 mm), if using the op- | |
| tional hood, and at least 36" (900 mm) if the hood is not | |
| used. |
|
Notch
The blower cord can be routed to either side after removing the ash lip and base cover. Route the cord to right or left by placing the cord in the proper notch shown above.
Do Not Connect This Unit To A Chimney Serving Another Appliance
Masonry Fireplace Requirements
1.The chimney must be at least 15 feet high but not more than 33 feet high.
2.This room heater must be connected to a code approved masonry chimney with a clay tile or stainless steel flue liner.
3.The entire fireplace and chimney must be clean and in good condition. Any damage must be repaired before installing the insert. A stainless steel liner may be in- stalled if the tile liner of the masonry chimney is dam- aged.
4.The fireplace and chimney must meet local building
codes.11