R

2700-I WOOD INSERT (ACT)

MASONRY FIREPLACE

USING DIRECT-CONNECT METHOD

The Quadra-Fire 2700-I Insert conforms with the UL Stan- dard for Safety 1482 and ULC S628 (Canada) in all respects, and is approved to UL & ULC safety standards for installa- tion and use within a fireplace with a masonry chimney in accordance with NFPA 211, with a direct flue collar connec- tion. A starter pipe is required to reach to the bottom of the existing flue.

1.Secure the fireplace damper in the open position. If this cannot be accomplished, it will be necessary to remove the damper.

2.Seal the damper area around the chimney liner with a high temperature sealant.

3.The chimney should be examined for cracks, loose mortar, and other signs of deterioration and blockage. The insert should not be installed until it is determined that the chimney is safe for use. Since an oversized flue contributes to the accumulation of creosote, the size of the flue should be checked to determine that it is not too large for the insert. The chimney should also be checked to ensure it meets the minimum standard of the National Fire Protection Association (NFPA) Standard 211. The following bullets list the more critical requirements for a properly constructed chimney:

The masonry wall of the chimney, if brick or modular block, must be a minimum of 4 inches (102mm) nominal thickness. A chimney of rubble stone must be at least 12 inches (305mm) thick.

The chimney must have a fire clay flue liner (or equiva- lent) with a minimum thickness of 5/8 inch (16mm) and must be installed with refractory mortar. An equivalent liner must be a listed chimney liner system or other approved material.

A chimney inside the house must have at least 2 inches (51mm) of clearance to the combustible structure. A chim- ney outside the house must have at least 1 inch (25mm) clearance to the combustible structure. Non-combustible fire stops must be installed at the spaces where the chim- ney passes through floors and/or ceiling (See Figures 7.1 and 7.2 on page 7).

NOTE: In Canada, a full reline is required.

WARNING

Fire Risk.

Inspection of Chimney:

Chimney must be in good condition.

Meets minimum standard of NFPA 211

Factory-built chimney must be 6 inch (152mm) UL103 HT.

Masonry

 

Chimney

 

Flue Tile

Full Listed

Mantel

Liner Option

 

Direct Connect

 

Seal Option

Damper

 

Area

 

 

SEAL DAMpER AREA

Figure 9.1 - Installation Into Masonry Fireplace

METAL HEAT CIRCULATING masonry

The Quadra-Fire 2700-I Insert conforms with the safety stan- dard UL-1482 and ULC S628 (Canada) in all respects and is approved to UL & ULC safety standards for installation and use within a fireplace with masonry chimney, in accordance

with NFPA 211, with a direct flue collar connection.

Mantel

Listed Liner

SEAL DAMpER AREA

Figure 9.2 - Installation Into Metal Heat Circulating Showing

Use Of Starter Pipe

WARNING

Fire Risk.

Do NOT pack insulation or other combustibles between spacers.

ALWAYS maintain specified clearances around venting and spacers.

Install spacers as specified.

Failure to keep insulation or other material away from vent pipe may cause fire.

September 1, 2008

7007-161H

Page

Page 9
Image 9
Hearth and Home Technologies 2700-I warranty Masonry Fireplace Using DIRECT-CONNECT Method, Metal Heat Circulating masonry