Heat & Glo • 6000GL-IPI-R, 6000GL-IPI-S • 2102-900 Rev. O • 12/0820
D. Mantel and Wall Projections
WARNING! Risk of Fire! Comply with all minimum clear-
ances as speci ed. Framing or nishing material closer than
the minimums listed must be constructed entirely of noncom-
bustible materials (i.e., steel studs, concrete board, etc).
Combustible Mantels
Combustible Mantel Legs or Wall Projections
MEASUREMENTS FROM
TOP EDGE OF THE OPENING
5
10
11
12
2-1/2
13 14
15 16 17 1819
32
TO CEILING
91011 12
8
7
6
5
4
3
25
18 AB
INTERIOR WALL
TOP VIEW
MANTEL LEG OR WALL PROJECTIONS
FIREPLACE OPENING
Note: All measurements in inches.
If A minimum is ____, then B maximum is_____.
AInches 2-7/16 3-7/16 4-7/16 5-7/16 6-7/16 7-7/16
Millimeters 62 87 113 138 164 189
BInches 12345
Millimeters 25 51 76 102 127
Note: Measurement is taken from top of the
opening, NOT the top of the replace.
Figure 5.4 Clearances to Mantel Legs or Wall Projections
(Acceptable on both sides of opening.)
Figure 5.3 Minimum Vertical and Maximum Horizontal
Dimensions of Combustibles