E. Install Outside Air Kit

Keep duct runs short and straight to minimize restriction.

The outside air kits must be installed on both sides of the fireplace.

WARNING! Outside air kits must be installed on both sides of the fireplace to prevent overheating and fire.

Locate the outside air hoods in a clear area.

Install as shown in Figures 7.3, 7.4 and 7.5.

The air ducts may be run vertically.

The outside air hoods must be at least 3 ft (.91 m) below the top of the uppermost chimney section.

The outside air hoods can be painted to match/accent the color of the structure.

CAUTION! Risk of Fire or Asphyxiation! Do not draw outside combustion air from wall, floor or ceiling cavity, or enclosed spaces such as an attic or garage.

DO NOT place outside air hood close to exhaust vents or chimneys. Fumes or odor could be drawn into the room through the fireplace.

Locate outside air hood to prevent blockage from leaves, snow/ice, or other debris. Blockages could cause the unit to overheat.

NOTICE: The fireplace provides some outside air for combustion. Other methods may be necessary if more air is required.

Flexible Duct (not supplied)

Outside Air

 

Hood

2 Wire Ties

Figure 7.5 Outside Air Installation

Heatilator • Birmingham BIR42 • 4059-308 F • 11/08

23

Page 23
Image 23
Hearth and Home Technologies BIR42 owner manual Install Outside Air Kit, Outside Air Installation