Hearth and Home Technologies ESCAPE-42DV owner manual ft V1 + V2 + H1 = 50 ft 15.2 m Max

Models: ESCAPE-42DV

1 57
Download 57 pages 27.42 Kb
Page 16
Image 16

2. Top Vent - Vertical Termination

No Elbow

NOTE: A flue restrictor can only be used in vent runs that include no elbows and exceed 30 ft. total of straight vertical.

V1 = 50 ft. Max. (15.2 m)

V1 = 3 ft. Min. (914mm)

FLUE

RESTRICTOR

FLUE RESTRICTOR

V1

Figure 5.6

Two Elbows

NOTE: A flue restrictor can only be used in vent runs that include no elbows and exceed 30 ft. total of straight vertical.

Note: Must have a 24 inches minimum vertical vent before attaching any elbow to the unit.

 

V1

 

H1

V2

2 ft

 

610 mm

1 ft

305 mm

*

3 ft

 

914 mm

3 ft

914 mm

*

4 ft

 

1.2 m

4 ft

1.2 m

*

 

 

 

 

 

 

5 ft

 

1.5 m

9 ft

2.7 m

*

 

 

 

 

 

 

6 ft

 

1.8 m

12 ft

3.7 m

*

V1 + V2 + H1 = 50 ft (15.2 m) Max.

*No specific restrictions on this value EXCEPT V1 + V2 + H1 cannot exceed 60 ft (18.3 m).

After V1 = 6 ft, then H1 Max.= V1 x 2

Figure 5.7

16

Heat & Glo • Escape-42DV2052-900 Rev. R • 10/08

Page 16
Image 16
Hearth and Home Technologies ESCAPE-42DV owner manual ft V1 + V2 + H1 = 50 ft 15.2 m Max