D. Vent Diagrams
WARNING
Fire Risk. Explosion Risk.
Do NOT pack insulation or other combustibles between ceiling firestops.
•ALWAYS maintain specified clearances around venting and firestop systems.
•Install wall shield and ceiling firestops as specified.
Failure to keep insulation or other material away from vent pipe may cause fire.
1. Top Vent - Horizontal Termination
One Elbow
NOTE: A flue restrictor can | Note: Must have a 24 | inches |
only be used in vent runs that | minimum vertical vent | before |
include no elbows and exceed | attaching any elbow to the unit. | |
30 ft. total of straight vertical. |
|
|
V1
H1
V1 Minimum | H1 | Maximum | ||
2 ft | 610 mm | 7 in* |
| 178 mm |
3 ft | 914 mm | 2 ft |
| 610 mm |
4 ft | 1.2 m | 4 ft |
| 1.2 m |
|
|
|
|
|
5 ft | 1.5 m | 9 ft |
| 2.7 m |
|
|
|
|
|
6 ft | 1.8 m | 12 ft |
| 3.7 m |
7 ft | 2.1 m | 14 ft |
| 4.3 m |
10 ft | 3.0 m | 20 ft |
| 6.1 m |
|
|
|
|
|
20 ft | 6.1 m | 40 ft |
| 12.2 m |
After V1= 6 ft then H1 = 2 x V ft Maximum
V1 + H1 = 60 ft Maximum
*when used with approved termination caps
Figure 5.3
Two Elbows
NOTE: A flue restrictor can |
|
|
|
| Note: Must have a 24 | inches | |
only be used in vent runs that |
| minimum vertical vent | before |
include no elbows and exceed |
| attaching any elbow to the unit. | |
30 ft. total of straight vertical. |
|
|
|
|
| ||
|
|
|
|
V1 Minimum | H1+ H2 | ||
3 ft | 914 mm | 18 in | 457 mm |
4 ft | 1.2 m | 3 ft | 914 mm |
|
|
|
|
5 ft | 1.5 m | 7 ft | 2.1 m |
|
|
|
|
6 ft | 1.8 m | 10 ft | 3.0 m |
7 ft | 2.1 m | 12 ft | 3.7 m |
10 ft | 3.0 m | 18 ft | 5.5 m |
|
|
|
|
20 ft | 6.1 m | 20 ft | 6.1 m |
|
|
|
|
After V1= 6 ft then H1 = 2 x V1 ft Maximum
V1 + H1 + H2= 60 ft Maximum
H1 + H2= 20 ft Maximum
H2H1
INSTALLED
HORIZONTALLY
Figure 5.4
V1
14 | Heat & Glo • |