NOVUS
F. UTILITIES
1.HIGH ALTITUDE INSTALLATION
For U.S. installation, appliances are tested and approved for elevations from
For Canada, appliances are certified for elevations from
2.GAS LINE CONNECTION
The appliance is provided with a stainless steel flexible connector and manual shutoff valve. See Figure 12. The incoming gas line should be piped into the valve compartment and connected to the 1/2” FIP connection provided on the manual shutoff valve. See Figure 13. All connections must be tightened and checked for leaks with a soap and water solution or leak detector. Bleed the gas line to extract any air that may have been trapped inside the pipe.
Note: The appliance and its manual shutoff valve must be disconnected from the gas supply piping system dur- ing any pressure testing of that system at test pressures in excess of 1/2 psi (3.5 kPa). The appliance must be isolated from the gas supply piping system by closing its manual shutoff valve during any pressure testing of the gas supply piping system at test pressures equal to or less than 1/2 psi (3.5 kPa).
3.GAS PRESSURE
On the standing pilot gas control valve and the electronic valve, a pressure tap is included on the front face of the valve.
Table 2 shows optimum gas pressure information.
Consult your local gas company for assistance in determining the proper orifice for your altitude or refer to ANSI
4.FUEL
Do not burn wood or other material in this appliance.
Natural or propane gas conversions necessary to meet the application need to be made by a qualified technician using Hearth & Home Technologies specified and approved parts.
In the event your standing pilot appliance must be converted to use propane gas, you must use a CKVP conversion kit. To convert to use natural gas, you must use a CKVN conversion kit.
If your intermittent pilot appliance must be converted to use natural gas, you must use a DCKN conversion kit. To convert to propane, use a DCKP conversion Kit.
Figure 12 - Flexible Connector and Manual
Shutoff Valve
Figure 13 - Gas Line
WARNING!
This valve has been preset at the factory. Altering settings may result in fire hazard or bodily injury.
TABLE 2
NOVUS
Inlet gas Supply pressure - N.G. | 4.5 (Min.) - 7.0 (Max.)* | |
|
| |
Optimum Manifold pressure - N.G. | 3.5* | |
|
| |
Inlet Gas Supply pressure - L.P. | 11.0 (Min.) - 14.0 (Max.)* | |
|
| |
Optimum Manifold pressure - L.P. | 10.0* | |
|
|
|
Input Rate - N.G. | GNBC30 | 25,000 BTU/hr. |
|
|
|
| GNBC33 | 25,000 BTU/hr. |
|
|
|
| GNBC36 | 27,000 BTU/hr. |
|
|
|
Input Rate - L.P. | GNBC33/36 | 25,000 BTU/hr. |
|
|
|
| GNBC30 | 24,000 BTU/hr. |
|
| |
Orifice Size - N.G. GNBC36 | .101 in./2.56 mm | |
|
|
|
| GNBC30/33 | .096 in./2.43 mm |
|
|
|
Orifice Size - L.P. | GNBC30/33/36 | .059 in./1.50 mm |
|
| |
* inches/water column |
|
11 | 34615 Rev G |