Heat & Glo LifeStyle 6000TR-OAK-IPI Minimum Clearances for Terminations, = Vent Terminal

Models: 6000TR-OAK-IPI

1 35
Download 35 pages 14.85 Kb
Page 26
Image 26
= VENT TERMINAL

G X = AIR SUPPLY INLETR

v

D = AREA WHERE TERMINAL IS NOT PERMITTEDAFigure 29. Minimum Clearances for Terminations H Manual background

 

E

 

 

 

 

 

 

 

 

v

 

 

 

 

 

 

 

L

B

 

 

 

U.S.

 

 

 

 

B

 

 

 

 

v

 

 

 

 

 

v

B

(3 FT)

 

 

 

v

 

 

 

 

 

 

 

 

 

F

v

 

v

I

M

v

 

 

 

 

 

 

 

X

 

 

 

 

 

 

 

 

 

 

 

A

 

 

 

J or K

M

N

P

Q

(See Note 2)

V

T

VS Electrical Service

D*

V

S Manual background V

V

= VENT TERMINAL

X = AIR SUPPLY INLET

= AREA WHERE TERMINAL IS NOT PERMITTED

A

=

12"

clearances above grade, veran-

K

 

=

3 ft. (U.S.A.)

 

 

 

 

 

 

 

(See Note 1)

da, porch, deck or balcony

 

 

 

6 ft. (Canada)

clearance to a mechanical

B

=

12"

clearances to window or door

 

 

 

 

 

 

 

air supply inlet

 

 

 

that may be opened, or to per-

L**

=

7 ft

 

clearance above paved

 

 

 

manently closed window.

 

 

 

(See Note 1)

 

sidewalk or a paved driveway

D*

=

18"

vertical clearance to unventilat-

 

 

 

 

 

 

 

located on public property

M*** =

18"

 

 

 

clearance under veranda,

 

 

 

ed soffit or to ventilated soffit lo-

 

 

 

 

 

 

cated above the terminal

 

 

 

 

 

 

 

porch, deck, balcony or over-

 

 

 

 

 

 

 

 

 

 

hang

 

 

*30”

for vinyl clad soffits and below

 

 

 

 

 

 

 

 

 

 

 

 

42”

 

vinyl

 

 

 

electrical service

N

 

=

6”

 

non-vinyl sidewalls

F

=

9"

clearance to outside corner

 

 

 

12”

 

vinyl sidewalls

G

=

6"

clearance to inside corner

P

 

=

8 ft.

 

 

 

 

 

H

=

3 ft. (Canada)

not to be installed above a gas

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

QMIN

 

RMAX

 

 

 

 

meter/regulator assembly within

 

 

 

 

 

 

 

 

 

 

 

 

1 cap

 

 

3 feet

 

2 x Q ACTUAL

 

 

 

 

3 feet (90cm) horizontally from the

 

 

 

 

 

I

=

3 ft. (U.S.A.)

center-line of the regulator

 

2 caps

 

 

6 feet

 

1 x Q ACTUAL

 

clearance to gas service regu-

 

3 caps

 

 

9 feet

 

2/3 x Q ACTUAL

 

 

 

6 ft. (Canada)

 

4 caps

 

12 feet

 

1/2 x Q ACTUAL

 

 

 

 

lator vent outlet

 

 

 

 

J

=

9" (U.S.A.)

 

QMIN = # termination caps x 3

RMAX = (2 / # termination caps) x QACTUAL

 

 

 

 

 

 

12" (Canada)

clearance to non-mechanical air

S

=

 

6"

 

 

clearance from sides of elec-

 

 

 

supply inlet to building or the

 

 

 

(See Note 5)

 

trical service

 

 

 

combustion air inlet to any other

T

=

12"

 

 

clearance above electrical

 

 

 

appliance

 

 

 

 

 

 

 

 

(See Note 5)

 

service

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

**a vent shall not terminate directly above a sidewalk or paved driveway which is located between two single family dwellings and serves both dwellings.

***only permitted if veranda, porch, deck or balcony is fully open on a minimum of 2 sides beneath the floor, or meets Note 2.

NOTE 1: On private property where termination is less than 7 feet above a sidewalk, driveway, deck, porch, veranda or balcony, use of

a listed cap shield is suggested.

NOTE 2: Termination in an alcove space (spaces open only on one side

and with an overhang) are permitted with the dimensions specified for

vinyl or non-vinyl siding and soffits. 1. There must be 3 feet minimum

between termination caps. 2. All mechanical air intakes within 10 feet of a termination cap must be a minimum of 3 feet below the termination cap. 3. All gravity air intakes within 3 feet of a termination cap must be a minimum of 1 foot below the termination cap.

Figure 29. Minimum Clearances for Terminations

NOTE 3: Local codes or regulations may require different clearances.

NOTE 4: Termination caps may be hot. Consider their proximity to doors or other traffic areas.

NOTE 5: Location of the vent termination must not interfere with access to the electrical service.

WARNING: In the U.S: Vent system termination is NOT permitted

in screened porches. You must follow side wall, overhang and

ground clearances as stated in the instructions.

In Canada: Vent system termination is NOT permitted in screened porches. Vent system termination is permitted in porch areas with two or more sides open. You must follow all side walls, overhang and ground clearances as stated in the instructions.

Heat & Glo assumes no responsibility for the improper perfor- mance of the fireplace when the venting system does not meet these requirements.

CAUTION: IF EXTERIOR WALLS ARE FINISHED WITH VINYL SIDING, IT IS SUGGESTED THAT A VINYL PROTECTOR KIT BE INSTALLED.

26

Heat & Glo • 6000TR-OAK, 6000TR-OAK-IPI383-901 Rev. K • 5/06

Page 26
Image 26
Heat & Glo LifeStyle 6000TR-OAK-IPI owner manual Minimum Clearances for Terminations, = Vent Terminal, X = Air Supply Inlet