Heat Controller DMH24DB-1, DMC24DB-1 manual Charging, Max elevation

Models: DMC24DB-1 DMH24DB-1

1 35
Download 35 pages 26.68 Kb
Page 33
Image 33

Charging

Charging

Each outdoor unit is factory charged (nameplate charge) for the evaporator as well as a 7.5m(25ft) line set for each indoor line.

Any time total line set is used either shorter or longer then the nominal 22.5m(75ft: for tri-zone) line set length the refrigerant charge has to be adjusted.

Whether the line set is made shorter or longer you must adjust the charge based on how many ft of tubing are either added or removed based on 20g(0.22oz) of R-410A per meter(foot).

 

Max total length

Max length of

Min length of

Max Elevation

Max elevation

Additional

 

between each indoor

Capacity (Btu/h)

of all pipes

between indoor

each pipe (A/B)

each pipe (A/B)

unit and outdoor unit

Refrigerant

 

(A+B)

 

 

(h1)

units (h2)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

24k

30m(100ft)

15m(50ft)

3m(10ft)

7.5m(25ft)

7.5m(25ft)

20g/m(0.22oz/ft)

 

 

 

 

 

 

 

Example: A 80ft line set is used for dual - zone 5 additional ft X 0.22 ounces per foot= add 1.1 ounces of R-410A

Important:

If you are ever uncertain of the unit charge, reclaim, evacuate and weigh in the correct charge using the unit nameplate charge adjusting for line sets longer or shorter than 7.5m(25ft) for each indoor unit. Unit is critically charged.

Service Manual 33