Performance Data

Heat Controller, Inc.

HBH Series

Submittal Data

 

 

 

Performance Data

Selection Notes

For operation in the shaded area when water is used in lieu of an anti-freeze solution, the LWT (Leaving Water Temperature) must be calculated. Flow must be maintained to a level such that the LWT is maintained above 42°F [5.6°C] when the JW3 jumper is not clipped (see example below). This is due to the potential of the refrigerant temperature being as low as 32°F [0°C] with 40°F [4.4°C] LWT, which may lead to a nuisance cutout due to the activation of the Low Temperature Protection. JW3 should never be clipped for standard range equipment or systems without antifreeze.

Example:

At 50°F EWT (Entering Water Temperature) and 1.5 gpm/ton, a 8 ton unit has a HE of 72,200 Btuh.

To calculate LWT, rearrange the formula for HE as follows:

HE = TD x GPM x 500, where HE = Heat of Extraction (Btuh); TD

=temperature difference (EWT - LWT) and GPM = U.S. Gallons per Minute.

TD = HE / (GPM x 500)

TD = 72,200 / (12 x 500)

TD = 12°F

LWT = EWT - TD

LWT = 50 - 12 = 38°F - Antifreeze must be used

HBH096

 

WATER/BRINE

 

 

Heating - EAT 70°F

 

 

 

 

 

 

 

 

 

 

EWT

FLOW

PD

PD ft.

HC

kW

HE

LAT

COP

°F

gpm

psi

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

12.0

1.7

4.0

96.7

7.17

72.2

95.9

4.0

50

18.0

4.5

10.3

101.9

7.27

77.1

97.4

4.1

 

24.0

7.9

18.2

104.7

7.32

79.8

98.2

4.2

 

 

 

 

 

 

 

 

 

In this example, a higher flow rate will be required for EWTs at or below 50°F without antifreeze.