Heat Controller VMH 18 Heat Controller, Inc, Installation Manual, Refrigerant Pipe Connection

Models: VMH 12 VMH 09 VMH 36 VMH 18 VMH 27

1 19
Download 19 pages 34.21 Kb
Page 11
Image 11
REFRIGERANT PIPE CONNECTION

Heat Controller, Inc.

INSTALLATION MANUAL

VMH InverterFlex Mini-Split

REFRIGERANT PIPE CONNECTION

Drain joint installation

Fit the seal into the drain elbow, then insert the drain joint into the base pan hole of outdoor unit, rotate 90Drain joint installation to securely assemble them.

Connecting the drain joint with an extension drain hose (locallyL lly purchased)), isn recommendedcase of the water. draining off the outdoor unit during the heating mode.

Seal

Drain joint

Base pan hole of

 

 

outdoor unit

Seal

Drain pipe

Refrigerant pipe connection

1. Flaring work

Main cause for refrigerant leakage is due to defect in the flaring work. Carry out correct flaring work using the following procedure:

A: Cut the pipes and the cable.

1.Use thelinepipingset kitkitoracoppercessorytubes/pipesor pi es purchaseded locallylocally..

2.Measure the distance between the indoor and the outdoor unit.

3.Cut tthepipes/tubesipes a little longera littlethanlongerthethan measuredthe measureddistancedistance. .

4.Cut the cablele 11.5m.5mlongerlongerthanthanthethepipipe/e tubelengthlength. .

B:Burr removal

1.Completely remove all burrs from the cut cross section of pipe/tube.

2.Put the end of the copper tube/pipe in a downward direction as you remove burrs in order to avoid dropping burrs into the tubing.

C:Putting nut on

Remove flare nuts attached to indoor and outdoor unit, then put them on pipe/tube having completed burr removal.(not possible to put them on after flaring work)

Fig.46

90

Oblique Roughness

Burr

Fig.47

Pipe

Reamer

Point down Refrigerant pipe connection1. Flaring work

Fig.48

Flare nut

Copper tube

Fig.49

10

Page 11
Image 11
Heat Controller VMH 18 Heat Controller, Inc, Installation Manual, Refrigerant Pipe Connection, Refrigerant pipe connection