Heat Controller VMH 36 Refrigerant Pipe Connection, Tightening Connection, Installation Manual

Models: VMH 12 VMH 09 VMH 36 VMH 18 VMH 27

1 19
Download 19 pages 34.21 Kb
Page 12
Image 12
Refrigerant Pipe Connection

VMH InverterFlex Mini-Split

INSTALLATION MANUAL

Heat Controller, Inc.

Refrigerant Pipe Connection

D: Flaring work

Firmly hold copper pipe in a die in the dimension shown in the table below.

Outer diameter

A in. (mm)

in. (mm)

 

 

Max.

Min.

o 1/4" (6.35)

0.5 (1.3)

0.276 (0.7)

o 3/8" (9.35)

0.63 (1.6)

0.394 (1.0)

 

 

 

o 1/2" (12.7)

0.709 (1.8)

0.394 (1.0)

Tightening Connection

Align the center of the pipes.

Sufficiently tighten the flare nut with fingers, and then tighten it with a spanner and torque wrench as shown in Fig.51 & 52.

Outer

Tightening

Additional tightening

Diameter

torque

torque

o 1/4" (6.35)

11.57 ft-lb

14.46 ft-lb

(160 kgf-cm)

(200 kgf-cm)

 

o 3/8" (9.35)

21.69 ft-lb

25.3 ft-lb

(300 kgf-cm)

(350 kgf-cm)

 

o 1/2" (12.7)

36.17 ft-lb

39.78 ft-lb

(500 kgf-cm)

(550 kgf-cm)

 

Caution

Excessive torque can break nut depending on installation conditions.

11

Page 12
Image 12
Heat Controller VMH 36 Refrigerant Pipe Connection, Tightening Connection, VMH InverterFlex Mini-Split, D Flaring work