VMH InverterFlex | INSTALLATION MANUAL | Heat Controller, Inc. |
Refrigerant Pipe Connection
D: Flaring work
Firmly hold copper pipe in a die in the dimension shown in the table below.
Outer diameter | A in. (mm) | |
in. (mm) |
|
|
Max. | Min. | |
o 1/4" (6.35) | 0.5 (1.3) | 0.276 (0.7) |
o 3/8" (9.35) | 0.63 (1.6) | 0.394 (1.0) |
|
|
|
o 1/2" (12.7) | 0.709 (1.8) | 0.394 (1.0) |
Tightening Connection
•Align the center of the pipes.
•Sufficiently tighten the flare nut with fingers, and then tighten it with a spanner and torque wrench as shown in Fig.51 & 52.
Outer | Tightening | Additional tightening | |
Diameter | torque | torque | |
o 1/4" (6.35) | 11.57 | 14.46 | |
(160 | (200 | ||
| |||
o 3/8" (9.35) | 21.69 | 25.3 | |
(300 | (350 | ||
| |||
o 1/2" (12.7) | 36.17 | 39.78 | |
(500 | (550 | ||
|
Caution
Excessive torque can break nut depending on installation conditions.
11