Heatcraft Refrigeration Products H-IM-82C Keypads, Preliminary Configurations, Normal Operation

Models: H-IM-82C

1 26
Download 26 pages 45.06 Kb
Page 13
Image 13
Keypads

PRO3 Top Mount Packaged Refrigeration System Outdoor

Keypads

 

NORMAL OPERATION

 

 

 

BUT. NO.

pressing

pressing

START UP

the button

with other

 

alone

buttons

 

 

 

 

 

pressed

 

 

 

 

 

together

 

 

 

 

more than

with 3

 

 

 

 

activates/

 

 

 

1

3 s: switch

 

deactivates

 

 

ON/OFF

 

 

 

 

the

 

 

 

 

 

 

 

 

 

 

continuous

 

 

 

 

 

cycle

 

 

 

 

- 1 s:

 

 

 

 

 

displays/

 

 

 

 

 

sets the set

 

 

 

 

 

point

 

 

 

 

 

- more

 

 

 

 

 

than 3 s:

 

 

 

 

 

accesses

 

 

 

 

 

the

 

for 1 s

 

 

2

parameter

RESET

 

 

setting

current EZY

 

 

 

 

 

pressed

 

menu

 

set

 

 

 

 

together

 

(enter

 

 

 

 

 

 

 

(2 and 3)

 

password

 

 

 

 

 

 

 

activate

 

22)

 

 

 

 

 

 

 

parameter

 

- mutes the

 

 

 

 

 

 

 

reset

 

audible

 

 

 

procedure

 

alarm

 

 

 

 

 

(buzzer)

 

 

 

 

 

 

pressed

 

 

 

 

more

together

 

 

 

 

with 1

for 1 s

 

 

 

than 3 s:

 

 

 

activates/

displays

 

 

3

activates/

 

 

deactivates

firmware

 

 

 

deactivates

 

 

 

the defrost

the

version

 

 

 

continuous

 

 

 

 

 

cycle

 

 

 

Preliminary Configurations

Once the electrical connections have been completed, simply power-up the controller to make it operative.

Heatcraft recommends that you check the parameters listed.

 

Control Parameters

 

 

st

set point

 

 

 

 

rd

set point differential

 

 

 

 

 

 

 

 

 

 

 

Defrost Parameters

 

 

d0

type of defrost

 

 

 

 

 

 

dl

interval between two defrosts

Controllers

 

 

dt

Alarm Parameters

end defrost temperature

 

 

dP

maximum defrost duration

 

 

 

 

3.

 

 

Ad

temperature alarm delay

 

 

 

 

 

 

AL

low temperature alarm threshold/deviation

 

 

 

 

 

 

AH

high temperature alarm threshold/deviation

 

 

 

 

 

 

Functions Available from Keypad

ON AND OFF

Switching the instrument ON: press UP for more than 3 s (when pressing the button, the display shows ON).

Switching the instrument OFF: press UP for more than 3 s. The display shows the message “OFF”, alternating with the temperature measured by the set probe.

In off status, the following functions are disabled (if featured by the model):

compressor control / duty setting / continuous cycle;

defrost;

fan control;

alarms : ‘LO’, ‘HI’, ‘IA’, ‘cht’, ‘CHT’;

door switch (A4= 7/8 );

buzzer (when available)

While the following are enabled:

temperature display, alternating with the message “OFF”;

parameter display and setting;

alarms: “E0”, “E1”, “E2”;

the internal timer relating to parameter ‘dI’ is updated. If ‘dI’ expires in OFF status, a defrost is performed when restarting;

auxiliary relay management, only in the following configurations:

H1= = 1/2 (“E0” alarm only)

H1= 3, A4= 6;

13

Page 13
Image 13
Heatcraft Refrigeration Products H-IM-82C Keypads, Preliminary Configurations, Functions Available from Keypad, the button