SET POINT SETTING (DESIRED TEMPERATURE VALUE)

WARNING: When first connected, easy is already on and ready to be used. The instrument can be switched on from a supervisor PC and via an external contact (setting A4= 5). The latter has priority over the other modes.

SET POINT SETTING (DESIRED TEMPERATURE VALUE)

The easy and easy compact devices control the desired temperature (set point) inside the cabinet or cold room directly and dynamically.

To view and modify the set point:

press SET for 1 s, the set value will start flashing;

increase or decrease the value using UP or DOWN;

press SET to confirm the new value.

3.Controllers

 

MANUAL DEFROST

 

 

Press DOWN for more than 3 s (activated only if the temperature

 

conditions are right).

 

 

 

CONTINUOUS CYCLE

 

Press UP+DOWN for more than 3 s (activated only if the temperature

 

conditions are right).

 

The continuous cycle is used to maintain refrigeration active in the

 

cabinet or cold room, regardless of the temperature inside the unit.

 

This may be useful for rapidly bringing the temperature below the

 

set point value.

 

 

 

RAPID DISPLAY OF THE TEMPERATURE READ BY THE OTHER

 

PROBES

 

Press the DOWN button to scroll the temperatures read by the

 

probes. Each time the DOWN button is pressed, the display will

 

show the name of the probe Pr1, Pr2 or Pr3 (only on the models

 

with 3 inputs and with multifunction input configured as a probe)

 

and after 1 s the temperature measured by the selected probe will

 

be displayed.

 

To display the other probes, press DOWN again.

 

To return to the normal display, wait 3 s without pressing any

 

buttons (exit by timeout).

Temperature Display

The temperature displayed, the unit of measure and the decimal resolution can be set according to the following parameters: /4, /5 and /6.

/4 : select probe displayed

Used to choose whether to display the temperature read by the control probe (Probe 1), Probe 2 or the status of the multifunction input (analogue or digital).

Parameter /4 selects the probe shown on the display, all the other display and control modes remain unchanged.

IMPORTANT: the easy compact models can display up to 2 probes.

Installation and Operations Manual

/5: select °C/°F

Defines the unit of measure used for temperature control. /5=0 to work in °C

/5=1 to work in °F.

WARNING:

when changing from one unit of measure to the other, all the values of the temperature parameters are modified to the new unit of measure.

The max and min limits of the absolute temperature parameters are the same for both °C that °F. The range of temperatures allowed is therefore different between °C and °F:

/6: disable decimal point

Used to enable or disable the temperature display with the resolution to the tenths of a degree between -20 and + 20 (easy) or -10 and +10 (easy compact).

/6= 0 temperature displayed to the tenth of a degree;

/6=1 temperature displayed without the tenths of a degree.

NOTE: the decimal point is only disabled in relation to the reading shown on the display (the calculations performed by the controller remain unchanged).

Temperature Control

The following parameters are used to control the temperature: St, r1, r2, r3, r4 and rd.

St: set point, r1 minimum value and r2 maximum value of the set point

Parameter St determines the desired temperature to be maintained inside the cabinet or cold room (set point). Parameters r1 (minimum value) and r2 (maximum) set the range of temperatures for setting the set point.

NOTE: the set point can be set by pressing the SET button (see par. “Setting the set point (desired temperature value)” page 11).

r3: select direct/reverse operation

Defines the operating mode of the device:

r3=0: direct with defrost. Used to request the activation of the compressor when the temperature measured by probe 1 rises above the set point. This mode also includes defrost

r3=1: direct without defrost

r3=2: reverse without defrost. Used to request the activation of the compressor when the temperature measured by probe 1 falls below the set point. This mode does NOT include defrost.