Heatcraft Refrigeration Products H-IM-82C Troubleshooting, Installation and Operations Manual

Models: H-IM-82C

1 26
Download 26 pages 45.06 Kb
Page 18
Image 18
Troubleshooting

Installation and Operations Manual

Troubleshooting

The following table shows a number of situations that may occur on the various models.

The most frequent causes and corresponding checks are described:

3.Controllers

Problem

Cause

Checks

 

 

 

 

 

the compressor does not start (signalled by

• compressor delay set defrost post

parameters c0, c1 and c2 and dd

the compressor LED flashing)

• dripping in progress

 

 

 

 

 

 

 

 

 

 

 

 

the temperature is over the set limits but

alarm delay set

parameters Ad, c6, d8

 

 

there is no alarm message and the buzzer, if

 

 

 

 

fitted, does not sound

 

 

 

 

 

 

 

alarm IA is signalled (multifunction input)

the multifunction input generates an alarm

connection of the input and whether this is

without actually being active

when the contact opens

closed in normal operation

 

 

 

 

 

 

 

the alarm connected to the multifunction

alarm delay set or parameter programming

1. if A4=1

 

 

input is not detected

error

2. the status of digital input A7

 

 

 

 

 

 

 

 

 

the defrost is not activated

defrost duration too short (dP)

parameters dP and dI

 

 

 

interval between defrosts dI=0: in this case

 

 

 

 

the defrost is not activated

 

 

 

 

 

 

 

the end defrost temperature is too low or

parameters dt and d/ (defrost probe)

 

the evaporator temperature is too high

 

 

 

the manual defrost is not activated and the

compressor protection times set

parameter d9 (select d9=1)

 

 

defrost LED flashes

 

 

 

 

 

 

 

 

 

the high temperature alarm is shown after a

the alarm delay after defrost is too short or

parameters d8 and AH

 

 

defrost

the alarm threshold is too low

 

 

 

 

 

 

 

 

the display remains frozen even after the

the ambient temperature has not yet

wait or reduce d8

 

 

defrost

reached the set point or alternatively the

 

 

 

 

time d8 has not elapsed

 

 

 

 

 

 

 

 

after modifying a parameter the controller

the instrument has not updated the old

turn the instrument off

and

on again or

continues working with the old values

value or alternatively the parameter setting

alternatively reprogram

the

parameters

 

procedure has not been ended correctly by

correctly

 

 

 

pressing the SET button for 3 s

 

 

 

 

 

 

 

 

the evaporator fan does not start 1.

1. a compressor and fan start delay has been

1. parameter c0

 

 

 

set

 

 

 

 

2. if F0=1 (fan managed by fan controller)

2. parameters F0, F1, Fd, dd and d/

 

 

 

• the evaporator is “hot”: the evaporator

 

 

 

 

temperature can be read by selecting

 

 

 

 

parameter /d;

 

 

 

 

• dripping in progress;

 

 

 

 

• F1 (evaporator fan control set point) too

 

 

 

 

low.

 

 

 

 

post-dripping delay set

 

 

 

 

3. if F0=0

3. parameters F0, F2, dd and Fd

 

 

• F2=1 and the compressor is off

 

 

 

 

• dripping in progress

 

 

 

 

post-dripping in progress

 

 

 

 

 

 

 

 

18

Page 18
Image 18
Heatcraft Refrigeration Products H-IM-82C Troubleshooting, Installation and Operations Manual, Controllers, Problem, Cause