Image 19
Device Setup

PRO3 Top Mount Packaged Refrigeration System Outdoor

Device Setup

Set 1 - Low Temperature Models - L6 w/ -10° F Set Point

Set o

Set 1

Set 2

Set 3

Set 4

 

 

 

 

 

Parameter

 

Description

Min

Max

Default

 

 

 

 

 

 

 

 

 

St

 

Set point

-30

30

-10

r1

 

Minimum set point value

-50

303

-30

r2

 

Maximum set point value

-30

150

30

c2

 

Minimum compressor off time

0

100

4

do

 

Type of Defrost

0

4

0

dI

 

Interval between defrost

0

199

6

dt

 

End defrost temperature set point

-50

127

65

dP

 

Maximum defrost duration ALARM_ED

1

199

60

d4

 

Defrost on power-up

0

1

1

dd

 

Dripping time

0

15

2

F0

 

Enable evaporator fan control

0

1

0

F2

 

Stop evaporator fan if compressor off

0

1

0

F3

 

Evaporator fan status during defrost

0

1

1

Fd

 

Post-dripping time

0

15

2

Set 2 - Medium Temperature Models - M6 w/ 34° F Set Point

Set o

Set 1

Set 2

Set 3

Set 4

 

 

 

 

 

Parameter

 

 

Description

Min

Max

Default

 

 

 

 

 

 

 

 

 

 

St

 

 

Set point

0

50

34

r1

 

 

Minimum set point value

-50

50

0

r2

 

 

Maximum set point value

0

150

50

c2

 

 

Minimum compressor off time

0

100

4

do

 

 

Type of Defrost

0

4

0

dI

 

 

Interval between defrost

0

199

6

dt

 

 

End defrost temperature set point

-50

127

65

dP

 

 

Maximum defrost duration ALARM_ED

1

199

60

d4

 

 

Defrost on power-up

0

1

1

dd

 

 

Dripping time

0

15

2

F0

 

 

Enable evaporator fan control

0

1

0

F2

 

 

Stop evaporator fan if compressor off

0

1

0

F3

 

 

Evaporator fan status during defrost

0

1

1

Fd

 

 

Post-dripping time

0

15

0

Set 3 - High Temperature Models - H6 w/ 38° F Set Point

Set o

Set 1

Set 2

Set 3

Set 4

 

 

 

 

 

Parameter

 

 

Description

Min

Max

Default

 

 

 

 

 

 

 

 

 

 

St

 

 

Set point

0

50

38

r1

 

 

Minimum set point value

-50

50

0

r2

 

 

Maximum set point value

0

150

50

c2

 

 

Minimum compressor off time

0

100

4

do

 

 

Type of Defrost

0

4

2

dI

 

 

Interval between defrost

0

199

6

dt

 

 

End defrost temperature set point

-50

127

40

dP

 

 

Maximum defrost duration ALARM_ED

1

199

40

d4

 

 

Defrost on power-up

0

1

0

dd

 

 

Dripping time

0

15

0

F0

 

 

Enable evaporator fan control

0

1

0

F2

 

 

Stop evaporator fan if compressor off

0

1

0

F3

 

 

Evaporator fan status during defrost

0

1

0

Fd

 

 

Post-dripping time

0

15

0

3. Controllers

19

Page 19
Image 19
Heatcraft Refrigeration Products H-IM-82C Device Setup, Set 1 - Low Temperature Models - L6 w/ -10 F Set Point