Liquid Lines
Liquid lines should be sized for a minimum pressure drop to prevent “flashing”. Flashing in the liquid lines would create additional pressure drop and poor expansion valve operation. If a system requires long liquid lines from the receiver to the evaporator or if the liquid has to rise vertically upward any distance, the losses should be calculated to determine whether or not a heat exchanger is required. The use of a suction to liquid heat exchanger may be used to subcool the liquid to prevent flashing. This method of subcooling will normally provide no more than 20˚F subcooling on high pressure systems. The amount of subcooling will depend on the design and size of the heat exchanger and on the operating suction and discharge pressures. An additional benefit from the use of the suction to liquid type heat exchanger is that it can help raise the superheat in the suction line to prevent liquid return to the compressor via the suction line. Generally, heat exchangers are not recommended on
Hot Gas Defrost Systems
Hot Gas Defrost systems can be described as reverse cycle,
Refrigerant Piping
Install all refrigerant components in accordance with applicable local and national codes and in accordance with good practice for proper system operation. The thermostatic expansion valve must be the externally equalized type. It can be mounted inside the unit end compartment. Mount the expansion valve bulb on a horizontal run of suction line as close as possible to the suction header. Use the clamps provided with the valve to fasten the bulb securely so there is a tight
Suction lines should be sloped towards the compressor at the rate of one
(1)inch per ten (10) feet for good oil return. Vertical risers of more than four
(4)feet should be trapped at the bottom with a
Reverse Cycle System
The hot gas unit coolers can be used in reverse cycle hot gas defrost systems using multiple evaporators connected to one condensing unit. Generally, not more than
See the piping view in the Reverse Cycle Defrost Piping diagram. The suction line check valve directs the hot gas through the drain pan loop which prevents condensate in the pan from freezing. The hot gas exits the loop at the pan loop outlet header and enters the evaporator through the check valve assembly. As the hot gas defrosts the coil, heat is removed from the hot gas and eventually it condenses into a liquid and exits the coil at the distributor side port. The liquid then flows through the check valve of the thermostatic expansion valve bypass assembly, around the thermostatic expansion valve, and into the system liquid line. The liquid refrigerant then feeds other evaporators on the cooling cycle, evaporates, and returns to the compressor through their suction lines.
Three Pipe System
The three pipe system (sometimes called
Alternating Evaporator System
In the alternating evaporator hot gas defrost system, a third line is taken off the compressor discharge line as the
IMPORTANT:
It is imperative that with the alternating evaporator hot gas defrost system, no more that 25% of the operating refrigeration load be in defrost at any time.
Hot gas line sizes for R-22, R404A and R507
System Capacity |
| Equivalent Discharge Length (Ft.) |
| ||||
BTU/Hr | 25 | 50 | 75 | 100 |
| 150 | |
4,000 | 1/2 |
| 1/2 | 1/2 | 1/2 |
| 1/2 |
5,000 | 1/2 |
| 1/2 | 1/2 | 1/2 |
| 1/2 |
6,000 | 1/2 |
| 1/2 | 1/2 | 5/8 |
| 5/8 |
7,000 | 1/2 |
| 1/2 | 5/8 | 5/8 |
| 5/8 |
8,000 | 1/2 |
| 5/8 | 5/8 | 5/8 |
| 5/8 |
9,000 | 1/2 |
| 5/8 | 5/8 | 5/8 |
| 5/8 |
10,000 | 1/2 |
| 5/8 | 5/8 | 5/8 |
| 5/8 |
12,000 | 5/8 |
| 5/8 | 5/8 | 7/8 |
| 7/8 |
14,000 | 5/8 |
| 5/8 | 7/8 | 7/8 |
| 7/8 |
16,000 | 5/8 |
| 5/8 | 7/8 | 7/8 |
| 7/8 |
18,000 | 5/8 |
| 7/8 | 7/8 | 7/8 |
| 7/8 |
20,000 | 5/8 |
| 7/8 | 7/8 | 7/8 |
| 7/8 |
25,000 | 7/8 |
| 7/8 | 7/8 | 7/8 |
| |
30,000 | 7/8 |
| 7/8 | 7/8 |
| ||
35,000 | 7/8 |
| 7/8 |
| |||
40,000 | 7/8 |
|
| ||||
45,000 | 7/8 |
|
| ||||
50,000 | 7/8 |
|
| ||||
60,000 |
|
| |||||
70,000 |
|
| |||||
80,000 |
|
| |||||
90,000 |
|
| |||||
100,000 |
|
|
Note: Use next larger hot gas line size for
REVERSE CYCLE DEFROST PIPING |
|
TXV
EVAP. COIL
CHECK
VALVE
CHECK VALVE
PAN LOOP
LIQUID
LINE
HEAT – X
CHECK VALVE | SUCTION | |
LINE | ||
|
TXV CHECK
VALVE
PAN LOOP
HEAT – X
EVAP. COIL
HOT GAS LINE
LIQUID LINE SUCTION LINE