Unit Cooler Piping

Pipe size example:

Given: -10°F Freezer with one system having (2) evaporators

One condensing unit rated at 24,000 BTUH’s @ -20°F SST R404A refrigerant.

Two evaporators each rated at 12,000 BTUH’s @ 10°F TD.

100 feet of actual line run between condensing unit to first evaporator and 20 feet of actual line run between the first evaporator and the second evaporator (see figure below).

How to figure line sizes:

1.Determine equivalent line run = actual run + valves and fitting allowances.

2.Use Line Sizing Tables to size lines.

3.Note any special considerations.

Evap. 2

Evap. 1

Fittings in this system:

(6) 90° elbows in main line plus a 90° turn through a tee.

(5) addtional 90° elbows to first evaporator.

(4) additional 90° elbows to second evaporator.

Determine line size 1 (main line from condensing unit):

1.Main line from the condensing unit to be sized for the total capacity (balance) of the whole system of 24,000 BTUH’s (Table 8).

2.Refer to 24,000 @100 feet at -20°F SST R404A on the chart. You will find the suction line to be 1-3/8" and 1/2" liquid line.

3.Refer to Table 5. For every 1-3/8" 90° elbow you must add 4 equivalent feet of pipe and 2.5 equivalent feet of pipe for each 1-3/8" tee.

Therefore, total equivalent line run =

Actual line run

100 feet

+ (6)

1-3/8" elbows @ 4'

24 feet

+ (1)

1-3/8" tee @ 2.5'

2.5 feet

Total equivalent line run

126.5 feet

4.Refer to Table 8. For 126.5 total equivalent feet, the suction line size should be 1-3/8" and the liquid line stays at 1/2" line.

Note: The gray shaded areas on Table 8. For 24,000 BTUH’s, the maximum suction riser is 1-1/8" to insure proper oil return and pressure drop from the bottom p-trap to the top p-trap.

Determine line size 2 (evaporators):

1.Line sizing to each evaporator is based on 12,000 BTUH’s and equivalent run from condensing unit. First evaporator has an 105 ft. run and the second evaporator has a 120 ft. run.

2.Table 8 indicates 1-1/8" suction for the first evaporator and indicates 1-1/8" suction for the second evaporator.

3.Refer to Table 5. Each 1-1/8" 90° elbow adds 3 equivalent feet of pipe. Each 90° turn through a 1-1/8" tee adds 6 equivalent feet.

4.

Actual line run (evap 1)

105 feet

 

+ (5)

1-1/8" elbows @ 3'

15 feet

 

+ (1)

90° turn through tee @ 6'

6 feet

 

Total equivalent line run

126 feet

 

Actual line run (evap 2)

120 feet

 

+ (4)

1-1/8" elbows @ 3'

12 feet

 

Total equivalent line run

132 feet

5.Table 8 indicates 1-1/8" suction line and 3/8" liquid line from main line to both evaporators.

Line Sizing

The following Tables 7 and 8 indicate liquid lines and suction lines for all condensing units for R22, R404A, and R507.

When determining the refrigerant line length, be sure to add an allowance for fittings. See Table 5. Total equivalent length of refrigerant lines is the sum of the actual linear footage and the allowance for fittings.

Table 3. Weight of Refrigerants in Copper Lines During Operation (Pounds per 100 lineal feet of type "L" tubing)

Line Size O.D.

Refrigerant

Liquid Line

Hot Gas Line

 

Suction Line at Suction Temperature

 

(Inches)

-40˚F

-20˚F

0˚F

+20˚F

+40˚F

 

 

 

3/8

22

3.9

0.22

0.02

0.03

0.04

0.06

0.08

R507, 404A

3.4

0.31

0.03

0.04

0.06

0.09

0.13

 

1/2

22

7.4

0.41

0.03

0.05

0.07

0.11

0.15

R507, 404A

6.4

0.58

0.04

0.07

0.13

0.16

0.24

 

5/8

22

11.8

0.65

0.05

0.08

0.12

0.17

0.25

R507, 404A

10.3

0.93

0.07

0.11

0.17

0.25

0.35

 

7/8

22

24.4

1.35

0.10

0.16

0.24

0.36

0.51

R507, 404A

21.2

1.92

0.15

0.23

0.37

0.51

0.72

 

1-1/8

22

41.6

2.30

0.17

0.28

0.42

0.61

0.87

R507, 404A

36.1

3.27

0.26

0.39

0.63

0.86

1.24

 

1-3/8

22

63.5

3.50

0.27

0.42

0.64

0.93

1.33

R507, 404A

55.0

4.98

0.40

0.58

0.95

1.32

1.87

 

1-5/8

22

90.0

4.96

0.37

0.59

0.90

1.33

1.88

R507, 404A

78.0

7.07

0.56

0.82

1.35

1.86

2.64

 

2-1/8

22

156

8.61

0.65

1.03

1.57

2.30

3.26

R507, 404A

134

12.25

0.98

1.43

2.35

3.23

4.58

 

2-5/8

22

241

13.70

1.01

1.59

2.42

3.54

5.03

R507, 404A

209

18.92

1.51

2.21

3.62

5.00

7.07

 

3-1/8

22

344

18.95

1.44

2.28

3.45

5.05

7.18

R507, 404A

298

27.05

2.16

3.15

5.17

7.14

9.95

 

3-5/8

22

465

25.60

1.94

3.08

4.67

6.83

9.74

R507, 404A

403

36.50

2.92

4.25

6.97

19.65

13.67

 

4-1/8

22

605

33.40

2.53

4.01

6.08

8.90

12.70

R507, 404A

526

47.57

3.80

5.55

9.09

12.58

17.80

 

10

Page 10
Image 10
Heatcraft Refrigeration Products H-IM-CU warranty Unit Cooler Piping, Line Sizing

H-IM-CU specifications

Heatcraft Refrigeration Products has long been recognized as a leader in the refrigeration industry, and their H-IM-CU model is a prime example of innovative design and cutting-edge technology. The H-IM-CU is engineered to deliver exceptional performance and efficiency, catering to various commercial refrigeration needs.

One of the standout features of the H-IM-CU is its robust construction. The unit is designed with high-quality materials that ensure durability and long-lasting performance in demanding environments. This construction not only protects against wear and tear but also supports the reliable operation essential for business continuity.

The H-IM-CU incorporates advanced cooling technologies that enhance its efficiency. Equipped with a high-efficiency compressor, this model optimizes energy consumption, reducing operational costs while still maintaining optimal refrigerant temperatures. This energy-efficient design is particularly beneficial for businesses looking to minimize their carbon footprint and achieve sustainability goals.

An important characteristic of the H-IM-CU is its user-friendly control system. The intuitive interface allows operators to easily adjust and monitor temperature settings, ensuring that products are stored in favorable conditions. This user-centric design simplifies the management of refrigeration units, making it easier for staff to perform routine tasks.

Additionally, the H-IM-CU features a whisper-quiet operation, which is an advantage for businesses that prioritize a pleasant customer experience. This is achieved through effective sound-dampening technologies and smart engineering that minimize noise without compromising cooling performance.

Another significant highlight is the versatility of the H-IM-CU. It is suitable for a wide range of applications, from convenience stores to restaurants and supermarkets. This adaptability makes it a preferred choice for businesses seeking a reliable refrigeration solution that can cater to their specific needs.

Furthermore, the model boasts enhanced airflow technology that ensures even temperature distribution throughout the unit. This promotes efficient cooling and eliminates hotspots, keeping products at the desired temperature consistently.

Overall, the Heatcraft Refrigeration Products H-IM-CU stands out as a leading choice in commercial refrigeration. With its combination of durability, energy efficiency, user-friendly controls, quiet operation, and versatility, it meets the high standards of modern businesses looking for reliable cooling solutions. Investing in the H-IM-CU not only enhances product longevity but also aids in operational efficiency, making it a wise choice for any commercial refrigeration setup.