D. Frame the Fireplace
Figure 6.4 shows typical framing using combustible materials (2x4 lumber shown).
•Observe all required air space clearances to combustible materials as shown in Figure 6.1 & 6.2.
•Framing across the top of fireplace must be above top standoffs.
54 5/8 in. (1387 mm) *
22 1/2 in.
(572 mm) *
*If the interior of the chase will be drywalled, add the thick- ness to this measurement.
REQUIRED!
2 in. (51 mm) minimum air space
clearance around chimney
18 in. (457 mm)
minimum distance
from wall to
fireplace opening.
1/2 in. (13 mm) Clearance
Figure 6.4 Framing the Fireplace
1/2 in.
Drywall
(1080 mm)
22 1/2 in.
(572 mm) *
1/2 in. (13 mm)
Clearance
Heatilator • CL36D, CR36D • 12538 • Rev Z 7/12 | 21 |