Heatmaster 201 manual Mcba For Specialists Installer, Service Engineer, Pilot Mode, Pilot mode

Models: 201

1 28
Download 28 pages 23.53 Kb
Page 17
Image 17
PILOT MODE

PILOT MODE

Pilot mode

After you power down the appliance the screen displays Pilot mode, as shown in the figure above.

This is the standard MCBA mode. The MCBA automatically returns to this mode after 20 minutes if no keys have been pressed on the screen. Any parameters that were modified are then enabled.

The first character shows the current status of the boiler depending on the condition of both the boiler and the burner. The last 2 characters indicate the start temperature.

Status

Boiler function

Pilot, no demand for heat

Fan first, fan after

Ignition

 

Operation of the boiler burner for the heating

Operation of the boiler burner for the domestic hot

water

 

Air pressure limit or obtaining the number of start

revolutions.

The burner goes out when the specified value is

reached. A demand for heat is present nonetheless.

Pump over-run time after the demand for domestic

hot water

 

Pump over-run time after the demand for central

heating

 

Burner blocked:

:T1 > 95°C

:T2 > 95°C

: T2 - T1 > 10.20 or 40°C after a time of xx

: dT1/dt > maximum gradient T1

: water pressure switch not off

: no fan signal

: erroneous fan signal

: T1 - T2 > max Delta

: NTC3 short-circuit

: NTC3 interrupt

: wait for the fan to start

If the burner is blocked for one of the reasons mentioned above, the screen display alternates between a 9 followed by the temperature (two last digits) and b with the error code.

MCBA FOR SPECIALISTS: INSTALLER, SERVICE ENGINEER

Once the cause of the blockage has been resolved, the burner starts automatically within 150 seconds at most.

Status

Boiler function

Internal check — three-way valve

Boiler burner in hot water ready function

Test function: Central heating high power

Test function: Central heating low power

Test function: Boiler with fixed number of revolutions

15

Page 17
Image 17
Heatmaster 201 manual Mcba For Specialists Installer, Service Engineer, Pilot Mode, Pilot mode