ELECTRICAL SUPPLY

CSL CSM CSB

ELECTRICAL SUPPLY

Standard electrical supply for all Combi-Steamers is 208-240 volt, 3 phase, 50-60 Hz.

NOTE: The power connections are located behind the service door (see section 5-3).

Each unit requires a separate fused service according to the following table: (3 phase only)

Model

Voltage

Phase

Amps

Load

CSL/M/B-6

208V

3

27

9.6KW

CSL/M/B-6

208V

1

46

9.6KW

CSL/M/B-6

240V

3

27

9.6KW

CSL/M/B-6

240V

1

40

9.6KW

CSL/M/B-10

208V

3

52

18.6KW

CSL/M/B-10

240V

3

45

18.6KW

CSL/M/B-1020

208V

3

88

31.5KW

CSL/M/B-1020

240V

3

76

31.5KW

CSL/M/B-20

208V

3

103

37.2KW

CSL/M/B-20

240V

3

90

37.2KW

CSL/M/B-40

208V

3

175

63KW

CSL/M/B-40

240V

3

152

63KW

NOTE: When the oven is installed it must be electrically grounded in accordance with local codes, or in the absence of local codes, with the National Electric Code, ANSI/NFPA 70-1990.

Do Not use conduit as a supply ground, or electrical shock could result.

NOTE: All connections must comply with the oven data plate. A separate fused disconnect switch or circuit breaker (not furnished) MUST be installed in the electrical supply line FOR EACH OVEN!

NOTE: The electrical diagram is located behind the service door.

The electric supply terminal block, located behind the service door, is clipped on a mounting rail which is attached to the frame of the unit. The three phases of the power cord are connected to the three gray colored terminals. Ground is con- nected to the yellow-green terminal.

NOTE: The phase sequence does not have to be observed because of the automatic reversing action of the fan motor.

CHANGES IN VOLTAGE

To change voltages of the Combi-Steamers (ex: 208 to 240 volt) the following has to be changed:

1)Air and steam elements

2)Contactor LS5

3)CSM and CSL units - the wires on the control panel transformer and the interior light transformer must be switched to the correct voltage terminals.