CSL CSM CSB
Installation – Electric Units (continued)
WATER SUPPLY
The
The recommended water supply pressure is 44 psi, but 22 to 87 psi will work.
Should the water pressure exceed 87 psi, a pressure regulator must be installed into the supply line or damage to the unit could result.
The water connection is done on a 3/4” NPT thread fitting, and a manual shut off valve must be installed between the main cold water supply and the units supply line.
A minimum water conductivity of 20 micro Siemens is required for proper operation. If below this figure the steam generator will
NOTE: A check valve is built into the unit to prevent backflow.
DRAIN CONNECTION
The
The unit has an integrated vented drain system which acts as a reverse flow check valve, so it may be connected directly with a
The drain must have a constant slope and a diameter of 2 inches over its entire length to ensure sufficient discharge during Auto Flush from the steam generator, which is 3/4 quarts per second.
The drain must be steam temperature resistant pipe, which average drain temperature is 150°F (65°C). No hose should be used.
65